4. Installing the refrigerant piping

A
B
45±2°
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D.
Flare dimensions
(mm)
øA dimensions (mm)
ø9.52
12.8 - 13.2
ø15.88
19.3 - 19.7
ø19.05
22.9 - 23.3
B
Refrigerant pipe sizes & Flare nut tightening torque
C
Do not apply refrigerating machine oil to the screw portions.
(This will make the flare nuts more apt to loosen.)
D
Be certain to use the flare nuts that are attached to the main unit.
(Use of commercially-available products may result in cracking.)
Liquid pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
P63
ODø9.52 (3/8")
34 - 42
P100
ODø9.52 (3/8")
34 - 42
* Connect the joint with the following pipes: Liquid and gas pipes of P50, gas pipe of P100/P125.
E Apply refrigerating machine oil over the entire flare seat surface.
„ PKFY-P·VKM-E
65
18.2
C
R407C or R22
Gas pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
ODø15.88 (5/8")
68 - 82
ODø19.05 (3-4")
68 - 82*
D
77
F
87
4.1. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
D
insulation materials (specific gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before
tightening flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
R410A
Liquid pipe
Tightening
Pipe size O.D.
torque.
(mm)
(N·m)
ODø9.52 (3/8")
34 - 42
ODø9.52 (3/8")
34 - 42
1170
444 ( A )*
482 ( B )
585 ( C )
1155
77
F
87
Fig. 4-2
4.2. Positioning refrigerant and drain piping (Fig. 4-2)
„ PKFY-P·VKM-E
A Gas pipe
* Indicates the condition with accessories mounted.
B Liquid pipe
C Drain hose
D Left-side piping knockout hole
E Right-side piping knockout hole
F Lower piping knockout hole
G Mount board 1
Flare nut O.D.
Gas pipe
Tightening
Liquid
Pipe size O.D.
torque.
pipe
(mm)
(N·m)
(mm)
ODø15.88 (5/8")
68 - 82
22
ODø15.88 (5/8")
68 - 82
22
295
65
123
154
134
71.2
Gas
pipe
(mm)
29
29
5
G
E
7

Publicité

Chapitres

Table des Matières
loading

Table des Matières