Installing The Refrigerant Piping; Precautions For Devices That Use R410A Refrigerant - Mitsubishi Electric Mr.Slim PUHZ-P-VHA2 Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18

4. Installing the refrigerant piping

A
45 2
A Flare cutting dimensions
B Flare nut tightening torque
Fig. 4-1
A (Fig. 4-1)
Copper pipe O.D.
Flare dimensions
(mm)
øA dimensions (mm)
ø6.35
ø9.52
12.8 - 13.2
ø12.7
16.2 - 16.6
ø15.88
19.3 - 19.7
ø19.05
23.6 - 24.0
B (Fig. 4-1)
Copper pipe O.D.
Flare nut O.D.
(mm)
ø6.35
ø6.35
ø9.52
ø12.7
ø12.7
ø15.88
ø15.88
ø19.05
A
Fig. 4-2
B
C
D
8.7 - 9.1
Tightening torque
(mm)
(N·m)
17
14 - 18
22
34 - 42
22
34 - 42
26
49 - 61
29
68 - 82
29
68 - 82
36
100 - 120
36
100 - 120
A
A Die
B Copper pipe
B
4.1. Precautions for devices that use R410A refriger-
ant
• Refer to page 3 for precautions not included below on using air condition-
ers with R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration
oil applied to the fl ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless
pipes, to connect the refrigerant pipes. Use refrigerant pipes with the
thicknesses specifi ed in the table to the below. Make sure the insides of
the pipes are clean and do not contain any harmful contaminants such as
sulfuric compounds, oxidants, debris, or dust.
Warning:
When installing or moving the air conditioner, use only the specifi ed refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
P100-P140
Liquid pipe
ø9.52 thickness 0.8 mm
Gas pipe
ø15.88 thickness 1.0 mm
• Do not use pipes thinner than those specifi ed above.
4.2. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specifi c gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-
ing fl are nut. A
• Use two wrenches to tighten piping connections. B
• Use leak detector or soapy water to check for gas leaks after connections are
completed.
• Apply refrigerating machine oil over the entire fl are seat surface. C
• Use the fl are nuts for the following pipe size. D
Gas side
Pipe size (mm)
Liquid side
Pipe size (mm)
• When bending the pipes, be careful not to break them. Bend radii of 100 mm to
150 mm are suffi cient.
• Make sure the pipes do not contact the compressor. Abnormal noise or vibration
may result.
1 Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-
plied on site).
• When usual pipe sealing is used, refer to Table 1 for fl aring of R410A refrigerant
pipes.
The size adjustment gauge can be used to confi rm A measurements.
Table 1 (Fig. 4-2)
Copper pipe O.D.
Flare tool for R410A
(mm)
ø6.35 (1/4")
1.0 - 1.5
ø9.52 (3/8")
1.0 - 1.5
ø12.7 (1/2")
1.0 - 1.5
ø15.88 (5/8")
1.0 - 1.5
ø19.05 (3/4")
1.0 - 1.5
P100-P140
ø15.88
ø9.52
A (mm)
Flare tool for R22·R407C
Clutch type
0 - 0.5
0 - 0.5
0 - 0.5
0 - 0.5
0 - 0.5
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr.slim puhz-p100vha2Mr.slim puhz-p140vha2

Table des Matières