Installation Location; Installing The Indoor Unit; Installing The Wall Mounting Fixture - Mitsubishi Electric CITY MULTI PKFY-P VKM-E Série Manuel D'installation

Masquer les pouces Voir aussi pour CITY MULTI PKFY-P VKM-E Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2. Installation location

„ PKFY-P·VKM-E
B
L
M
F
G
Fig. 2-1

3. Installing the indoor unit

1
2
4
5
Fig. 3-1
„ PKFY-P·VKM-E
F
H
15.5
0
25
50
75
100
117
125
142
192
242
279.5
292
C
E
A
K
Fig. 3-2
B
A
C
E
D
Fig. 3-3
(mm)
A
1170
C K
D
E
*
J
H
I
3
G
(mm)
A
100
I
J
A Sleeve
B Hole
C (Indoors)
D Wall
E (Outdoors)
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and
maintenance.
„ PKFY-P·VKM-E
A
B
Min. 100.5
Min. 22.4
F Air outlet: Do not place an obstacle within 1500 mm of the air outlet.
G Floor surface
H Furnishing
I When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
extra distance should be taken because the fan air current may create a short cycle.
J 1800 mm or greater from the floor surface (for high location mounting)
K 108 mm or greater with left or rear left piping and optional drain pump installation
L 550 mm or greater with optional drain pump installation
M Minimum 7 mm: 265 mm or greater with optional drain pump installation
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART NUMBER
ACCESSORY
1
Mount board
2
Tapping screw 4 u 25
3
Felt tape
4
L-shaped connection pipe
5
Charge nut

3.2. Installing the wall mounting fixture

3.2.1. Setting the wall mounting fixture and piping positions
X Using the wall mounting fixture, determine the unit's installation position
and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
B
„ PKFY-P·VKM-E (Fig. 3-2)
54
A Mount board 1
25
0
B Indoor unit
12.5
37.5
C Bottom left rear pipe hole (ø75-ø80)
62.5
87.5
104.5
D Bottom right rear pipe hole (ø75-ø80)
129.5
E Knockout hole for left rear hole (75 × 480)
167
217
F Bolt hole (4-ø9 hole)
229.5
G Center measurement hole (ø2.5 hole)
264
292
308.5
H Tapping hole (75-ø5.1 hole)
311
I Hole centre
D
J Align the scale with the line.
K Insert scale.
3.2.2. Drilling the piping hole (Fig. 3-3)
X Use a core drill to make a hole of 75-80 mm diameter in the wall in the
piping direction, at the position shown in the diagram to the left.
X The hole should incline so that the outside opening is lower than the
inside opening.
X Insert a sleeve (with a 75 mm diameter and purchased locally) through the
hole.
Note:
The purpose of the hole's inclination is to promote drain flow.
C
D
E
Min. 48
Min. 250
Min. 220
QUANTITY
LOCATION OF SETTING
P63
P100
1
1
7
7
2
2
Fix at the back of the unit
1
1
1
1
(mm)
3