Coverage testing has been performed according to the NEMA WD 7 guideline. For best performance, use in spaces not larger than
18' x 15'.
PIR Sensor
The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field of
view. The red LED on the sensor flashes when the PIR detects motion.
Masking the Lens
Opaque adhesive tape is supplied so that sections of the PIR sensor's view can be
masked. You can eliminate coverage in unwanted areas. Since masking removes
bands of coverage, take this into account when troubleshooting coverage problems.
Ultrasonic Sensor
The sensor has two ultrasonic transceivers operating at 40kHz. Detection sensitivity
can be adjusted using the trimpot under the ON/OFF buttons.
Side View
4'
(1.2m)
0
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the DW flying leads as shown in the wiring diagram below that is appropriate to the DW
model and electrical supply.
3. Attach the DW to the wall box by inserting screws into the two wide holes on the top and bottom of the
attached metal bracket. Match them up with the holes in the wall box and tighten.
4. Turn the circuit breaker ON. Wait one minute, then push the ON/OFF button for each load and the lights
will turn ON.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
DW-100 and DW-100-347 Wiring

COVERAGE PATTERNS

35'
20'
(10.6m)
(6.1m)
INSTALLATION
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Neutral
Line
Black
Blue
Neutral
White
Ground
Green
DW-200 Bi-Level Wiring
PIR
Coverage
35'
(10.6m)
(6.1m)
White
Neutral
Line 1
Primary
Red
Load
Line 2
Neutral
Brown
Secondary
Load
Neutral
3
Top View
Major motion
Minor motion
20'
7.5'
7.5'
(2.2m)
(2.2m)
15'
(3.0m)
(4.5m)
Black
Red
Blue
Brown
White
Ground
Green
DW-200 Dual Circuit Wiring
Major motion
Minor motion
Ultrasonic
Coverage
20'
(6.1m)
15'
(4.5m)
10'
#12 – #14 AWG
Strip Gage
1/2"
12.7mm
Cu Wire Only
White
Primary
Load
Secondary
Load