Fanox SIL A Manuel D'utilisation page 298

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

BINARY INPUT (OBJECT 1) -> Assigned to Class 0.
BINARY INPUT CHANGE (OBJECT 2) -> Assigned to Class 1.
Index
Description
105
50_1 Trip A
106
50_1 Trip B
107
50_1 Trip C
108
50_1 Trip P
109
50_2 Start A
110
50_2 Start B
111
50_2 Start C
112
50_2 Start P
113
50_2 Trip A
114
50_2 Trip B
115
50_2 Trip C
116
50_2 Trip P
117
51 Start N
118
51 Start A
119
51 Start B
120
51 Start C
121
51 Start P
122
51 Trip A
123
51 Trip B
124
51 Trip C
125
46BC Start
126
46BC Trip
127
74TC Trip
128
74TC Start
129
Trip Block
CONTROL RELAY OUTPUT BLOCK (OBJECT 12)
Index
Description
0
Lock/Unlock 79
1
52 open/close
2
LED Reset
3
49 Reset
ANALOG INPUT (OBJECT 30) -> Assigned to Class 0.
ANALOG INPUT CHANGE (OBJECT 32) -> Assigned to Class 2.
Index
Description
0
Phase A current
1
Phase B current
2
Phase C current
3
Phase A voltage
4
Phase B voltage
5
Phase C voltage
6
Active Power
7
Reactive Power
8
Frequency
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
www.fanox.com
Full Scale Range (Referenced to In=1A or In=5A)
0 to 6 / 0 to 1,2 Amps
0 to 6 / 0 to 1,2 Amps
0 to 6 / 0 to 1,2 Amps
0 to 76,2 Volts
0 to 76,2 Volts
0 to 76,2 Volts
0 to 228,6 / 0 to 1143 Watts
0 to 228,6 / 0 to 1143 Watts
0 to 60 / 0 to 72 Hz
Rev.19
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
298/301