BINARY INPUT (OBJECT 1) -> Assigned to Class 0.
BINARY INPUT CHANGE (OBJECT 2) -> Assigned to Class 1.
Index
Description
98
50_2 Trip A
99
50_2 Trip B
100
50_2 Trip C
101
50_2 Trip P
102
51 Start N
103
51 Trip N
104
51 Start A
105
51 Start B
106
51 Start C
107
51 Start P
108
51 Trip A
109
51 Trip B
110
51 Trip C
111
51 Trip P
CONTROL RELAY OUTPUT BLOCK (OBJECT 12)
Index
Description
0
Lock/Unlock 79
1
52 open/close
ANALOG INPUT (OBJECT 30) -> Assigned to Class 0.
ANALOG INPUT CHANGE (OBJECT 32) -> Assigned to Class 2.
Index
Description
0
Phase A current
1
Phase B current
2
Phase C current
3
Phase A voltage
4
Phase B voltage
5
Phase C voltage
6
Active Power
7
Reactive Power
8
Frequency
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
www.fanox.com
Full Scale Range (Referenced to In=1A or In=5A)
0 to 6 / 0 to 1,2 Amps
0 to 6 / 0 to 1,2 Amps
0 to 6 / 0 to 1,2 Amps
0 to 76,2 Volts
0 to 76,2 Volts
0 to 76,2 Volts
0 to 228,6 / 0 to 1143 Watts
0 to 228,6 / 0 to 1143 Watts
0 to 60 / 0 to 72 Hz
Rev.19
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).
(0 to 4095).