No Object (Delay Measurement)
11.3. Point list (Révision A)
BINARY INPUT (OBJECT 1) -> Assigned to Class 0.
BINARY INPUT CHANGE (OBJECT 2) -> Assigned to Class 1.
Index
Description
0
Protection active
1
Auxiliary input 1
2
Auxiliary input 2
3
Auxiliary input 3
4
Auxiliary input 4
5
Auxiliary input 5
6
Auxiliary input 6
7
Auxiliary input 7
8
Auxiliary input 8
9
Auto-recloser active
10
Teleprotection active
11
Local parameter setting
12
Trip circuit supervision
13
Start / pick-up L1
14
Start / pick-up L2
15
Start / pick-up L3
16
Start / pick-up N
17
General trip
18
Trip L1
19
Trip L2
20
Trip L3
21
General start / pick-up
22
Breaker failure
23
Trip I>>
24
Trip IN>>
25
CB 'on' by AR
26
AR blocked
27
CB close / open
28
52 Status Closed
29
52 Status Open Time
30
52 Status Open Failure
31
52 Status Close Failure
32
52 Status excessive openings
33
52 Status excessive sum of switched amperes
34
52 Status excessive openings per minute
35
52-A Status
36
52-B Status
37
52 Status Error
38
79 Status Reclose Time
39
79 Status Open
40
79 Status Wait Time
41
79 Status Reclaim Time
42
79 Status Security Time
43
79 Status final open Time
44
Start Trip Circuit Supervision