8 BATTERY FACTS

The battery is the only periodically serviceable parts in the UPS. An expected life is approx.
3∼5 years. However, frequent long discharges or ambient temperatures above 25°C (80°F)
will shorten battery life. Therefore, it is recommended to replace the batteries every 3 years
after initiating the unit.
Recharge batteries every 3 months is necessary if it is not in use because it may cause
batteries over-drain.
WARNING
Only a qualified technician should replace the battery. Batteries have high short-
circuit current capacity; mistakes in connecting or disconnecting can cause
connections to arc or weld and could cause severe burns.
STORAGE
The UPS should only be stored if the battery is fully charged. Avoid storage temperatures
above 25°C (80°F) as battery life is significantly shortened. Every 90 days remove the unit
from storage and plug it in for 24 hours to recharge the batteries. Batteries may be damaged
if left in storage and not recharge every 90 days.
IMPORTANT NOTICE
Please use same type and same rating of batteries for replacement.
Do not replace it with the battery that exceeds specified rating.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - France - www.infosec.fr
Hot Line : tél : +33(0)2 40 76 15 82 - fax : +33 (0)2 40 94 29 51- hotline@infosec.fr - 10 05 04 205 02
-
-