5 TROUBLE SHOOTING TABLE
Proceed as follows for quick detection of common faults.
DC loads must be disconnected from the batteries and the AC loads must be disconnected
from the inverter before the inverter and/ or battery charger is tested.
Consult your Victron Energy dealer if the fault cannot be resolved.
Problem
Cause
The inverter fails
The battery voltage is too high
to operate when
or too low.
switched on.
The inverter fails
Processor in no function-mode.
to operate
The alarm LED
Pre-alarm alt. 1. The DC input
flashes.
voltage is low.
The alarm LED
Pre-alarm alt. 2. The ambient
flashes
temperature is too high.
The alarm LED
Pre-alarm alt. 3. The load on the
flashes.
inverter is higher than the
nominal load.
The alarm LED
Pre-alarm alt. 4. Voltage ripple
flashes.
on the DC input exceeds
1.25Vrms.
The alarm LED
Pre-alarm alt. 5. Low battery
flashes
voltage and excessive load.
intermittantly.
The alarm LED is
The inverter did cut out following
on
a pre-alarm.
Solution
Ensure that the battery voltage
is within the correct value.
Disconnect mains voltage.
Switch Front switch off, wait 4
seconds
Switch front switch on.
Charge the battery or check the
battery connections.
Place the inverter in a cool and
well-ventilated room, or reduce
the load.
Reduce the load.
Check the battery cables and
terminals.
Check the battery capacity;
increase if necessary.
Charge the batteries, reduce
the load or install batteries with
a higher capacity. Use shorter
and/or thicker battery cables.
Check the table for the
appropriate course of action.