Installation Diagram; Indoor Unit; Installation Of The Outdoor Unit - Daikin Siesta ATXC25AV1B9 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 84

Indoor Unit

50mm or more from walls
(on both sides)
Titanium apatite deodorizing filter (2)
Filter frame
Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines
below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing one side
More than 50
Side View

INSTALLATION DIAGRAM

Front panel
M4 x 12L
Air filter
Titanium apatite
deodorizing filter
Air filter
Tab
Outdoor Unit

INSTALLATION OF THE OUTDOOR UNIT (25/35)

More than 100
1200 or
less
55mm or more from ceiling
Service lid
n Opening service lid
Service lid is opening/closing
type.
n Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Wall facing two sides
More than 50
Wall facing three sides
More than 50
1-6
Caulk pipe
Cut thermal insulation pipe to an
hole gap
appropriate length and wrap it with
with putty.
tape, making sure that no gap is left
in the insulation pipe's cut line.
Wrap the insulation pipe
with the finishing tape
from bottom to top.
More than 150
More
than 100
Top View
More than 150
More than 300
Top View
More than 50
Unit : mm

Publicité

Table des Matières
loading

Table des Matières