Phase Sequence Indication; Mains Wiring Test; Operating Ranges And Uncertainties Per En 61557 - Beha-Amprobe Telaris Série Guide D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 68

Phase Sequence Indication

Icon
Display of Phase Sequence
Mains Input Voltage Range
(phase-tophase)

Mains Wiring Test

Icons (
) indicate if L-PE or L-N terminals are reversed. Instrument operation is
inhibited and an error code is generated if the input voltage is not between 100 V and 500
V. The UK Loop and RCD tests are inhibited if the L-PE or the L-N terminals are reversed.

Operating Ranges and Uncertainties per EN 61557

FUNCTION
0,00 Ω - 2000 Ω
R
LO
R
0,00 MΩ - 1000 MΩ
ISO
Z
0,00 Ω - 2000 Ω
Z
I
Z
(HI CURRENT)
I
0,00 Ω - 2000 Ω
0,0 ms - 2000 ms
∆T, I
∆N
I
3 mA - 550 mA
∆N
Volts 0,0 VAC - 500 VAC
Phase
0,0 Ω - 2000 Ω
R
E
Displays "1-2-3" in digital display field for correct
sequence. Displays "3-2-1" for incorrect phase. Dashes in
place of a number indicate a valid determination could
not be made.
100 to 500 V
DISPLAY
MEASUREMENT RANGE
RANGE
OPERATING ERROR
200 MΩ - 1000 MΩ
(NO TRIP)
I
∆T
icon Phase Sequence indicator is active.
EN 61557
0,3 Ω - 2000 Ω
± ( 10% + 3 dgt )
1 MΩ - 200 MΩ
± ( 12% + 3dgt )
± ( 15% + 5 dgt )
0,5 Ω - 2000 Ω
± ( 15% + 8 dgt )
0,3 Ω - 200 Ω
± ( 10% + 5 dgt )
25 ms - 2000 ms
± ( 10% + 2 dgt )
3 mA - 550 mA
± ( 10% + 2 dgt )
50 VAC - 500 VAC
± ( 3% + 3 dgt )
10 Ω - 2000 Ω
± ( 10% + 3 dgt )
30
NOMINAL VALUES
4,0 VDC < U
< 12 VDC
Q
≤ 2,00 Ω I
≥ 200 mA
R
LO
N
U
= 100 / 250 / 500 / 1000 VDC
N
I
= 1,0 mA
N
U
= 230 / 400 VAC
N
f = 50 / 60 Hz
I
= 0 A - 10,0 kA
PSC
∆T@ 10 / 30 / 100 / 300 / 500 /
1000 mA
I
= 10 / 30 / 100 / 300 / 500 mA
∆N
U
= 230 / 400 VAC
N
f = 50 / 60 Hz
1 : 2 : 3
f = 123 Hz

Publicité

Table des Matières
loading

Table des Matières