Appendix 1: Wattmeter
Connect as shown in the following figures.
L1
N
Single-phase installation*
* A jumper must be connected between points 1 and 4 of the wattmeter.
The wattmeter must be installed downstream from the power consumption and production installation.
RS-485 communications are as indicated in the following table.
See Section "2.4. Description of Connection Points" for information on the connection with
INGECON EMS Manager.
A65+
Wattmeter with protective covers installed
A.
Connections
The protective covers give protection against direct electrical contact. These must be removed to make the
connections and reinstalled once the connections are made.
AAX2002IKH06_A - Installation manual
11
1
3
4
Connection
41
42
43
B.
Joystick
C.
11
1
L1
L2
L3
N
Three-phase installation
Signal
A
B
GND
1
2
3
4
5
E
31 32 33 41 42 43 51 52 53 54 55 56 57
A65+ wattmeter with protective covers removed
LED
D.
Selector
3
4
6
7
9
6
7
8
9 10 11 12 13
E.
Display
English - 39
Ingeteam
A
B
C
D