Appendix 1: Wattmeter; Connection - Ingeteam INGECON EMS Manager Manuel D'installation

Masquer les pouces Voir aussi pour INGECON EMS Manager:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 65
Ingeteam

Appendix 1: Wattmeter

INGECON EMS Manager must be installed with the A65 or A65+ wattmeter supplied by Ingeteam.
A65: wattmeter used in installations with a consumption of less than 15 kW per phase (equivalent to
65 A).
A65+: wattmeter used in three-phase installations with a consumption of more than 15 kW in any of
the phases (current transformers are required).
The value measured is transferred to the device via RS-485 series communications with the INGECON EMS
Manager in order to permanently adapt the user-required strategy to installation consumption.

Connection

Make all connections without voltage.
The wattmeter must be installed on the DIN rail.
A65
Wattmeter with protective covers installed
A.
Connections
The protective covers give protection against direct electrical contact. These must be removed to make the
connections and reinstalled once the connections are made.
38 - English
B.
Joystick
C.
11
E
41 42 43
3
31 32 33
A65 wattmeter with protective covers removed
LED
D.
Selector
Appendix 1: Wattmeter
1
4
7
6
9
E.
Display
AAX2002IKH06_A - Installation manual
A
B
C
D
A

Publicité

Table des Matières
loading

Table des Matières