FAULT-FINDING CHART

DEFECT
The burner does not start-up
The burner starts, the flame does
not form and it therefore blocks
The burner starts, the flame forms
and it therefore blocks
UK
CAUSE
a) No electrical power
b) Gas does not reach the burner
a) The gas valves do not open
b) There is no discharge between
the points of the electrodes
c) No air pressure switch consent
a) No or insufficient flame detection
by the control electrode
48
REMEDY
a) Control the power supply line fu-
ses. Control the thermostats and
gas pressure switch lines
b) Check the opening of the shut-
off devices positioned along the
supply piping.
a) Check valves functioning
b) Check ignition transformer fun-
ctioning and the positioning of
the electrode points
c) Check calibration and functioning
of the air pressure switch
a) Check the positioning of the con-
trol electrode.Control the value
of the ionisation current