Placement of Q-Tee II C
Installation distance from a combustible wall
The stove is placed on a non-combustible floor.
Using non insulated 150mm I.D. flue pipe, the minimum distance to combustible wall
must be 450 mm from the flue.
Normal set-up -
corner setting
A. Distance to furniture
(min.)
Distance to flammable materials (min.)
C. to the side (floor)
D. to the rear (wall)
E. to the side of the wall
E
If the stove is to be installed on a wooden floor, it must be covered
with a non-combustible material at least 12 mm thick, in accor-
dance with UK Building Regulations
Approved Document J. The stove is to be elevated min. 100 mm,
for example placed on a non-combustable base.
Distance to flammable materials (min.)
B. in front (floor) Stove
elevated 0 mm
B. in front (floor) Stove
elevated 100 mm
Without Reflector
E
D
attika
RAIS/
- User manual for RAIS Q-TEE II / Q-Tee II C
Uninsulated flue
1200 mm
national/local regulations are followed
300 mm
400 mm
465
300 mm
Insulated flue
1200 mm
if distances are not shown,
200 mm
400 mm
465
300 mm
With Reflector
E
Uninsulated flue
with Reflector
1200 mm
200mm
400mm
465
300 mm
23