Switch Interval; Source Of Required Value; Synchronous Control - Xylem HYDROVAR Smart Manuel Opérateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.21.4 Switch Interval

SWITCH INTERVAL
12 hours
Adjustable between 1 hour and 100 hours. If it is set higher than 100 hours, the
automatic changeover is deactivated).
Manual change of master pump in the 1
Press
on the Hydrovar-Smart to change to

7.21.5 Source of required value

SOURCE REQ. VALUE
Five settings are possible:
OFF, ADR1,ADR2, ADR3 and ADR4. If an additional input (INT or EXT-ADC-I or EXT-ADC-
U) is active, you must select the address where this input is connected.
When Multicontroller or Synch. Controller is active, the actual active value is shown in
brackets in the middle of the display. If the sign "#" is shown in the second line of the
display, the pump will work with a required value from another pump in the multipump
system. On the pump, which is the source of the required value, there is no "#" shown.
Press
on the Hydrovar-Smart to change to

7.21.6 Synchronous Control

If the synchronous control is active the activated pumps try to control the set pressure
together (all pumps run at the same frequency). The 2
reaches the release frequency (ENABLE SEQ. CONTR.) The pumps will now maintain
constant pressure by running synchronously. The follow-up pump will stop, when both
pumps together run below the set SYNCHRON. LIMIT. This creates the hysteresis effect.
S U B M E N U
Synch. Control
SYNCHRON. LIMIT
0,0 Hz
Switch off threshold of the first follow-up pump. The switch off thresholds of the other
pumps are each higher by the SYNCHRON-WINDOW.
This parameter is also used for the stop value for the external constant speed pump at
activated Simple Multicontroller in the parameter configuration relay.
Press
on the Hydrovar-Smart to change to
For changing the master pump and follow-up pump in
order to achieve even operating hours of the pumps
for selecting the pump address of the source of the
OFF
required value.
Press
submenu and the display changes to
7.21.6.1 Synchronous Limit
Frequency threshold adjustable between 0,0 Hz and
the set maximum frequency.
st
display with the
nd
pump starts, when the 1
for about 3 seconds to enter the
32
-button.
st
pump

Publicité