After connection of the Hydrovar-Smart unit to the power supply the following displays
become visible.
SW-Ver: HV00-001
Date:
The following two displays are depending on the selected mode:
a) Active MODE = Controller:
1.
Continue by pressing the
2.
REQUIRED VALUE 1
If several pumps are connected via the RS-485 interface, one pump must be ready for
operation when the set pressure is changed, otherwise the set value will not be accepted
by the follow-up pumps. Afterwards the new required pressure has to be saved in all
pumps.
If you want to change to Required Value 2 you have to close the external contact,
connected to X1/10-X1/14.
After closing this contact, the display changes from Required value 1 to
2.1
REQUIRED VALUE 2
ADC-X
ADC-X: This parameter shows the source of the external or internal value.
XX.X Bar: shows the actual value of the Required Value 2.
Continue by pressing the
xxxx
XYLEM
XX.X BAR
-button
X.XX BAR
XX.X BAR
-button (to point 3)
The current software version with the date of
programming is displayed for about 3s.
This window is mentioned several times in the
Operating Instructions as 1
Set the desired set pressure with either
then briefly press the
In this window, there is shown the condition of
the second Required value.
16
st
display at Mode Controller
or
-button.