Lenze CAN-I/O PT Instructions De Montage page 53

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

X3.1/
Designation
7
GND1
LO
CAN-LOW
HI
CAN-HIGH
X3.2/
Designation
E1
Digital input
E2
Digital input
X3.3/
Designation
7
GND1
39
GND2
28
CINH
20
EDK82ZAFCC-210 DE/EN/FR 4.0
Function
Reference potential 1
System bus LOW (data line)
System bus HIGH (data line)
Function
User-defined,
can alternatively be used as a frequency
input (see "Technical data")
User-defined
Function
Reference potential 1
Reference potential 2 for controller
inhibit (CINH) at X3.3/28
Controller inhibit
DC voltage source for internal supply of
controller inhibit (CINH)
Electrical installation
Terminal assignment
Level
Level
0 = LOW (0 ... +3 V)
1 = HIGH (+12 ... +30 V)
Reference: GND2
Level
Start = HIGH (+12 V ... +30 V)
Stop = LOW (0 V ... +3 V)
+ 20 V (Ref: GND1)
6
53

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E82zafcc210

Table des Matières