If you wish to recover the product serial numbers, tick the box « Load serial number» (2).
If this box is not ticked, the load will contain all the parameters of the system apart from the serial numbers.
Click on the « load » button to load the file (3)
5.6.

Pairing without a PC

In the case of "Mirror architecture", 2 ARF50 modules can be paired together using the ADEUNIS RF configurer.
Pairing may either be by radio (where the ARF50s are connected by radio modems), or by cable via the RS485.
The procedure is as follows:
A representation of the location of the miniDIP is given in § 3.3. "Description of terminal blocks".
Step 1: « Master»: Set the pairing miniDIP "Us" of switch 2 (Us/SW2) to ON
Step 2: Switch on the products
Step 3: « RF slave » : Set the Us/SW2 miniDIP to On then OFF
During this step the « RF slave » sends its serial number to the "Master"
Step 4 « Master »: Set the Us/ W2 miniDIP to OFF.
Pairing ARF50s without a PC only affects the memorisation of the product serial number. It does not
permit changes to the configuration of the ARF50 I/Os, nor the modem. The configuration software
must be used to change these parameters.

6. Modbus Communication

The Modbus protocol is used to connect a compatible GUI and to display the I/O values for the purposes of super-
vision.
Function code implemented:
– 0x03: read multiple output registers (maximum number of registers read by the command = 125).
– 0x04: read multiple input registers.
In «Modbus» mode, outputs can be controlled via the following function code:
– 0x10: write multiple registers.
Comment: the «Broadcast» address is not managed by the product.
208009A-V1.3-UG_ARF50
1
2
3
47