8.2.3.7.4 Zeroing ("Zero Setting")
You can use the "Zero-Set" function in the software of your IO-Link master to set zero.
Measured data continues to be outputted after the electronics has zeroed.
The zero point is not saved permanently; if you disconnect the device from the supply
voltage it will have to be zeroed again.
Index
Sub-
(hex)
index
(hex)
0x0C1B 0x00
0x0002
0x00
0x0002
0x00
8.2.3.7.5 Limit value switches (Switching Signal Channel 1 / Switching Channel 2)
There are two limit value switches that are executed as per the IO-Link Smart Sensor pro­
file specification (B.8.3 Quantity detection). Each limit value switch is a main item in the
"Parameters" menu. Their operation is identical.
S
Switch 1: SSC.1 (Switching Signal Channel 1)
S
Switch 2: SSC.2 (Switching Signal Channel 2)
36
Authorization Data type
ReadWrite
UIntegerT 1
ReadWrite
Float32T
Data
Authoriza­
type
tion
Read only
Float32T
Write
UInteger8T
Write
UInteger8T
Data
Name
size
(bytes)
Lowpass
Filter Mode
4
Lowpass
Filter Cut-off
Frequency
Data
Name
size
(bytes)
4
Zero
Offset
1
Zero -
Set
1
Zero -
Reset
Description
Activate/
deactivate filter
and select filter
characteristic
0 - No filter
50 - Bessel filter
51 - Butterworth
filter
Cut-off frequency
System
Description
command
(hex)
Current zero
value, as
defined by
"Zero Setting"
0xD0
Triggers zero­
ing
0xD2
Deletes the
zero memory