Start-Up, Operation, Maintenance; Start-Up/Putting Into Operation; Operation And Maintenance; Industrial Safety Instruction - VTS VOLCANO VR Mini Manuel D'installation, D'utilisation Et D'entretien

Publicité

MODEL
DIAGRAM
74
3
1
2
4

6. START-UP, OPERATION, MAINTENANCE

6.1 START-UP/PUTTING INTO OPERATION

Prior to any installation or maintenance works, disconnect the device from the power supply and secure it against accidental power-up.
Install vent valves at the highest point of the installation.
Install cut-off valves directly behind the device, so it can be easily disassembled.
Secure the device against pressure increase according to the permitted maximum pressure value of 1.6 MPa.
It is suggested to use additional external current differential protection.
NOTE All connections should be made according to this technical documentation and the documentation enclosed with the automatic devices.

6.2 OPERATION AND MAINTENANCE

Device casing does not require any maintenance.
side of the air guides (but the device does not need to be disassembled). Pay attention to the exchanger's lamellas, as these are delicate.
If lamellas bend, straighten them with a special tool.
The fan motor does not require any maintenance. It may only require cleaning of the protective mesh, fan blades and dust and grease deposits.
If the device is not used for a long time, disconnect the voltage supply.
It is recommended to periodically blow through the heat exchanger, preferably with compressed air.
The heat exchanger can freeze (fracture) when the room temperature falls below 0°C and the heating agent temperature decreases at the same time.
The level of air pollutants should meet the criteria allowable concentrations of pollutants in indoor air, for non-industrial areas, the level of dust concentration up to 0.3 g / m³. It is forbidden
to use device for the duration of the construction works except for the start-up of the system.
moisture content). The device should not be exposed to direct UV rays.
The device should be operated at the supply water temperature up to 130 ° C with working fan.

7. INDUSTRIAL SAFETY INSTRUCTION

Special instructions concerning safety NOTE
Prior to any work connected with the device, the device must be disconnected from the power supply and be secured properly. Wait until the fan stops.
Use stable assembly platforms and hoists.
Depending on the heating agent temperature, piping, parts of the casing, heat exchanger surface can be very hot, even after the fan stops.
There may be some sharp edges! During transport, use protective gloves, protective clothing and safety shoes.
The health and safety instructions must be followed.
Loads can be fastened only in places designed for it in a transport unit. While devices are lifted by an assembly unit, their edges need to be secured. Distribute the load evenly.
Disposal: Take care to dispose of used materials, packaging material and spare pars in a safe way, one which is not harmful to the environment and is in accordance with local regulations.
TECHNICAL DATA
WALL-MOUNTED WING/VR CONTROLLER
SPEED REGULATOR (0-10V)
Supply voltage: ~230/1/50
Permissible initial current: 0,02A for 0-10V
Working mode: manual
Output signal: 0-10VDC
Level of protection: IP 30
37
COMMENTS
programming device, is 100 m.
the min. size 5 x 1 mm2 or 6 x 1mm2 depend on the option of
connection (see the schemes)
visualisations of sample products.
an optional device, which may be replaced with any programming
device or switch that conforms to the 60335 standard.
Power connection should be done with a cable min. 3 x 0.75 mm 2.
Automation element drawings are only a visualisation of sample
products.
EN