VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D
4. ASSEMBLY
NOTE Installation location should be suitably selected with special consideration of potential loads and vibrations.
Prior to any installation or maintenance works, disconnect the device from the power supply and secure it against accidental power-up.
NOTE
mounting height
distance between units – recommended distance 6-12m (Volcano VR1, VR2, VR3), 3-7m (Volcano VR Mini), in order to ensure even hot air diffusion
EN
range of air stream
Max. 14m* (Volcano V mini)
Max. 22m* (Volcano VR1, VR2)
Max. 25m* (Volcano VR3)
Max. 28m* (Volcano VR-D)
device noise level (depending on acoustic characteristics of a room)
direction of air distribution should be controlled in a way that prevents draughts. Air stream must not be directed at walls, brackets, girders, cranes, shelves, machines, etc.
m
. 3 - 7
in i)
O P T
V R M
a n o
( V o lc
2 m
3 )
. 6 - 1
2 , V R
O P T
, V R
V R 1
a n o
( V o lc
Max. 2m** (Volcano V mini)
Max. 13m* (Volcano VR1, VR2)
Max. 15m* (Volcano VR3, VR-D)
32
* for vertical air guides adjustment
* for horizontal air guide adjustment
** for symmetric air guide adjustment at an angle of 45°