B
B
ATTERY
OX TECHNICAL DATA TABLE
BASIC MODELS
BATTERY
Nominal voltage
End of charge voltage
No. of batteries/V
SUNDRY
Ambient temperature (1)
Humidity
Protections
Dimensions H x L x D
Weight
(1) 20-25°C for extended battery life
T
ABLE OF OVERLOAD TIMES
OVERLOAD TIMES
100% < Load 125%
125% < Load 150%
Load > 150%
T
BBX SDL 240V BB NP A3
[Vdc]
[Vdc]
[°C]
[mm]
[Kg]
63
OPERATION FROM
BYPASS
Bypass active after 2 sec
Locked after 120 sec
Bypass active after 2 sec
Locked after 4 sec
Bypass active instantly
Locked after 1 sec
85
ECHNICAL DATA TABLE
BBX SDL 240V BB NP A5
240
273
20 / 12
0 – 40
< 90% non condensing
overcurrent - short circuit
455 x 175 x 660
INVERTER
Locked after 60 sec
Locked after 4 sec
Locked after 0.5 sec
65

Publicité