Supply Air Temperature Rise Test; Limit Control Check; Restart After Burner Failure; Maintenance - Dettson AMP112SD Guide D'installation Et Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

proper functioning (see instructions included with the damper.)
After the furnace has been firing for at least five minutes, the
draft regulator should be set to between -0.025" and -0.060"
W.C.
3.3.5 Overfire Pressure Test
The overfire draft that is taken through the observation port,
located above the burner, is a measurement necessary to
determine if there is a blockage in the heat exchanger or the
flue pipe. Refer to the Technical Specifications in this manual
for overfire pressure values. A high pressure condition may be
caused by excessive combustion air, due to the air band being
too wide open, or a lack of flue draft (chimney effect) or some
other blockage, such as soot in the secondary section of the
heat exchanger or the use of an oversize nozzle input or high
pressure pump.
3.3.6 Vent Temperature Test
After having adjusted the burner combustion, insert a
1.
thermometer into the test hole in the breech pipe;
The total vent temperature should be between 204 and
2.
302° C (400 and 575° F). If not, check for improper a ir
temperature rise, pump pressure, nozzle size or a badly
sooted heat exchanger.

3.3.7 Supply Air Temperature Rise Test

Operate the burner for at least 10 minutes;
1.
Measure the air temperature in the return air plenum;
2.
Measuring the air temperature in the largest trunk coming
3.
off the supply air plenum, just outside the range of radiant
heat from the heat exchanger. 0.3 m (12") from the
plenum of the main take-off is usually sufficient;
The temperature rise is calculated by subtracting the
4.
return air temperature from the supply air temperature;
If the temperature rise is lower or exceeds the
5.
temperature specified in Table 6, change to the next
lower or higher blower speed tap, until the temperature
rise falls to the target. If the excessive temperature rise
cannot be increased or reduced by changing fan speed,
investigate for ductwork obstructions, dirty or improper air
filter, improper firing caused by improper pump pressure
or nozzle sizing.

3.3.8 Limit Control Check

After operating the furnace for at least 15 minutes, restrict the
return air supply by blocking the filters or the return air register
and allow the furnace to shut off on High Limit. The burner will
shut off but the blower will continue to run.
Remove the obstruction and the burner should restart after a
few minutes. The time required for the restart also depends on
the adjustment of the blower "OFF" delay.

3.3.9 Restart After Burner Failure

Set the thermostat lower than room temperature;
1.
Press the reset button on the burner primary control
2.
(relay);
Set the thermostat higher than room temperature;
3.
If the burner motor does not start or ignition fails, turn off
4.
the disconnect switch and CALL A QUALIFIED SERVICE
TECHNICIAN.
Do not attempt to start the burner when excess oil has
accumulated, when the furnace is full of vapour or when
the combustion chamber is hot.
4

MAINTENANCE

Electrical shock hazard.
Turn OFF power and fuel to the furnace before any
disassembly or servicing.
Failure to do so can result in death, bodily injury
and/or property damage.
Preventive maintenance is the best way to avoid
unnecessary expense and inconvenience. Have your
heating system and burner inspected by a qualified
service technician at regular intervals.
To maintain the reliability and optimal performance of the
furnace, have a complete combustion check done after
the annual maintenance call. Do not attempt to repair the
furnace or its controls. Call a qualified service technician.
Before calling for repair service check the following
points:
1.
Check the oil tank gauge and make sure that the
valve is open;
2.
Check fuses and the circuit breaker;
3.
Check if the main disconnect switch is ON ;
4.
Set the thermostat above room temperature;
5.
If ignition does not occur, turn off the disconnect
switch and call a qualified service technician.
When ordering replacement parts, please specify the
complete furnace model number and serial number.
4.1

CLEANING THE HEAT EXCHANGER

It is not generally necessary to clean the heat exchanger
or flue pipe every year, but it is advisable to have the oil
burner service technician check the unit before each
heating season to determine whether the cleaning or
replacement of parts is necessary.
If a cleaning is necessary, the following steps should be
performed:
1.
Turn OFF all utilities upstream from the furnace;
2.
Disconnect the flue pipe;
3.
Remove the flue collar panel located at the front of
the furnace;
4.
Remove the heat exchanger baffles;
5.
Disconnect the oil line and remove the oil burner;
6.
Clean the secondary tubes and the primary cylinder
with a stiff brush and a vacuum cleaner;
7.
Before re-assembling the unit, the heat exchanger
and combustion chamber should be inspected to
determine if replacement is required;
11
CAUTION
WARNING

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Amp112svAmp série

Table des Matières