Models:
AMT098SD
AMT098SV
c
Manufactured by:
Dettson Industries Inc
3400, Industrial Boulevard
Sherbrooke, Qc, Canada, J1L 1V8
www.dettson.ca
Attention
Do not tamper with the unit
or its controls.
qualified service technician.
Printed in Canada on 100% recycled paper
All manuals and user guides at all-guides.com
Installation Instructions
and Homeowner's Manual
us
INSTALLER / SERVICE TECHNICIAN :
Use the information in this manual for the installation / servicing of the
furnace and keep the document near the unit for future reference.
HOMEOWNER :
Call a
Please keep this manual near the furnace for future reference.
LOW-BOY
OIL-FIRED FURNACE
2011-12-15
X40186 Rev. A

Publicité

loading

Sommaire des Matières pour Dettson AMT Serie

  • Page 1 Homeowner’s Manual LOW-BOY OIL-FIRED FURNACE Models: AMT098SD AMT098SV Manufactured by: Dettson Industries Inc 3400, Industrial Boulevard Sherbrooke, Qc, Canada, J1L 1V8 www.dettson.ca INSTALLER / SERVICE TECHNICIAN : Use the information in this manual for the installation / servicing of the Attention furnace and keep the document near the unit for future reference.
  • Page 2 All manuals and user guides at all-guides.com TABLE OF CONTENTS SAFETY REGULATIONS....................................3 SAFETY LABELING AND WARNING SIGNS ............................3 IMPORTANT INFORMATION ................................3 DETECTION SYSTEMS..................................3 DANGER OF FREEZING ..................................3 INSTALLATION ......................................4 POSITIONING THE FURNACE ................................4 ELECTRICAL SYSTEM ..................................4 ....................................4 ELECTRICAL SYSTEM .................................5 INSTALLATION OF THE THERMOSTAT INSTALLATION OF THE BURNER..............................5 VENTING .......................................5...
  • Page 3 All manuals and user guides at all-guides.com Before calling for service, be sure to have the information page of your manual close by in order 1 SAFETY REGULATIONS to be able to provide the contractor with the required information, such as the model and serial numbers of the furnace.
  • Page 4 All manuals and user guides at all-guides.com Figure 1: Location and dimensions of ventilation air openings in a closet door 2 INSTALLATION The unit is shipped with a burner and its controls. It requires a 115VAC power supply to the control panel and thermostat hook-up as shown on the wiring diagram, one or more oil line connections, suitable ductwork and connection to a properly sized vent.
  • Page 5 All manuals and user guides at all-guides.com INSTALLATION OF THE BURNER INSTALLATION OF THE THERMOSTAT Also refer to the burner manufacturer’s instructions. A thermostat must be installed to control the temperature of Position the mounting gasket between the mounting the area to be heated. Follow the instructions supplied with the flange and the burner mounting plate.
  • Page 6 All manuals and user guides at all-guides.com The burner must shut-off immediately, while the 2.6.1 ASONRY CHIMNEY blower continues to run to the end of the cool-down This furnace can be vented into an existing masonry chimney. cycle. However, the unit must not be vented into a chimney into If the test is not in line with the above, call a QUALIFIED which a solid fuel burning furnace is already being vented.
  • Page 7 All manuals and user guides at all-guides.com Solvent based glue; 2.10.1 IR FILTER Antistatic fabric softeners for clothes dryers; A properly sized air filter must be installed on the return air m. Acid based masonry cleaning materials. side of the unit. Refer to the Technical Specifications, p.13, for the correct dimensions.
  • Page 8 All manuals and user guides at all-guides.com Figure 6:Blower start / stop delays - Board #1158 2.12 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard. Turn OFF electrical power at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.
  • Page 9 All manuals and user guides at all-guides.com 3.3.2 RESSURE ADJUSTMENT 3 OPERATION The oil pressure must be adjusted according to the Technical Specifications of this manual. An adjustment screw and a connection for a pressure gauge are located START-UP on the oil pump for that purpose. Also refer to the burner instruction manual.
  • Page 10 All manuals and user guides at all-guides.com 3.3.5 3.3.9 VERFIRE PRESSURE TEST ESTART AFTER BURNER FAILURE The overfire draft that is taken through the observation port, Set the thermostat lower than room temperature; located above the burner, is a measurement necessary to Press the reset button on the burner primary control determine if there is a blockage in the heat exchanger or the (relay)
  • Page 11 All manuals and user guides at all-guides.com CLEANING THE HEAT EXCHANGER CLEANING OF THE BURNER HEAD It is not generally necessary to clean the heat exchanger or Once annually, remove the retention head and electrodes flue pipe every year, but it is advisable to have the oil burner from the drawer assembly and remove all foreign matter, if service technician check the unit before each heating season necessary.
  • Page 12 All manuals and user guides at all-guides.com 5 FURNACE INFORMATION Model: Serial number: Furnace installation date: Service telephone #-Day: Night: Dealer name and address: START-UP RESULTS Nozzle: Pressure: lb/po Burner adjustments: Primary air Fine air Drawer Assembly Smoke scale: (Bacharach) Gross stack temperature: °F Ambient temperature:...
  • Page 13 All manuals and user guides at all-guides.com Table 7:Technical Specifications UNITS WITH 1 /3 HP PSC MOTO R UNITS WITH 1/2 HP E CM MOTOR RATING AND PERFORMANCE Firin g r ate (USGP H) * 0.55 0 .70 0.55 0.70 Inpu t (BTU/h )* 77 000 98 00 0...
  • Page 14 All manuals and user guides at all-guides.com Table 8: Airflow Data, Models with 1/2 HP ECM motors OIL HEATING MODE 24 VAC input (R) on W only SW1- HEAT HEAT INPUT CFM with SW3-ADJ CFM with SW3-ADJ CFM with SW3-ADJ DIP switch position (USGPH) DIP switch position A...
  • Page 15 All manuals and user guides at all-guides.com Table 9: Airflow Data, Models with 1/3 HP PSC motors AM T0 98 E XTE RNAL STATIC P RE SSURE W ITH AIR FILTE R S PEE D 0.2" ( W .C.) 0.3" (W .C.) 0.4"...
  • Page 16 All manuals and user guides at all-guides.com Figure 7: Furnace Dimensions...
  • Page 17 All manuals and user guides at all-guides.com Figure 8: Wiring Diagram - 4 Speed Motor (PSC)
  • Page 18 All manuals and user guides at all-guides.com Figure 9: Wiring Diagram - Variable Speed Motor (ECM)
  • Page 19 All manuals and user guides at all-guides.com COMPONENTS REPLACEMENT PARTS...
  • Page 20 All manuals and user guides at all-guides.com Figure 10: Parts List - With 4 Speed motor PSC B50082E...
  • Page 21 All manuals and user guides at all-guides.com Table 11: Parts List - With 4 Speed motor PSC PART # DESCRIPTION COMMENTS ITEM B03540 HEAT EXCHANGER ASSEMBLY Heat exchanger only J06L002 EXTRUDED JOINT 1/4 X 1/8 X 25' B03570 FLOOR ASSEMBLY B03561 INSIDE WIRE CHANEL B03572...
  • Page 22 All manuals and user guides at all-guides.com Figure 11: Parts List - With variable speed motor ECM B50083E...
  • Page 23 All manuals and user guides at all-guides.com Table 12: Parts List - With variable speed motor ECM B03540 HEAT EXCHANGER ASSEMBLY Heat exchanger only J06L002 EXTRUDED JOINT 1/4 X 1/8 X 25' B03570 FLOOR ASSEMBLY B03561 INSIDE WIRE CHANEL B03572 LOWER DIVIDER ASSEMBLY Includes panel, 3 gaskets and baffle B03335-02...
  • Page 24 FOURNAISE AU MAZOUT “LOW-BOY” Modèles: AMT098SD AMT098SV Fabriqué par: Industries Dettson Inc 3400, Boulevard Industriel Sherbrooke, Qc, Canada, J1L 1V8 www.dettson.ca INSTALLATEUR / TECHNICIEN : Utiliser les renseignements dans ce manuel pour l’installation et l’entretien Attention de l’appareil et garder le document près de l’unité pour références Ne pas altérer votre unité...
  • Page 25 All manuals and user guides at all-guides.com Table des matières RÈGLES DE SÉCURITÉ................................3 SIGNALISATION DANGER, MISE EN GARDE ET AVERTISSEMENT ................3 REMARQUES IMPORTANTES ............................3 SYSTÈMES DE PROTECTION ............................3 RISQUE DE GEL .................................4 INSTALLATION ..................................4 EMPLACEMENT ................................4 É ..............................5 RACCORDEMENT LECTRIQUE INSTALLATION DU THERMOSTAT ..........................5 INSTALLATION DU BRÛLEUR ............................6 ÉVACUATION..................................6...
  • Page 26 All manuals and user guides at all-guides.com f) Demander à l’installateur d'identifier et de 1 RÈGLES DE SÉCURITÉ vous informer sur les items suivants : L’interrupteur d’alimentation électrique ; La valve d’arrêt sur le réservoir de SIGNALISATION DANGER, MISE EN mazout ;...
  • Page 27 All manuals and user guides at all-guides.com RISQUE DE GEL AVERTISSEMENT Cet appareil de chauffage central n’est pas AVERTISSEMENT étanche et n’est donc pas conçu pour Si votre appareil demeure fermé durant la saison l’extérieur. L’appareil doit être installé de façon froide, les conduites d’eau peuvent geler, éclater et à...
  • Page 28 All manuals and user guides at all-guides.com Figure 3:Branchement du thermostat-Chauffage et RACCORDEMENT ÉLECTRIQUE Climatisation-Unité avec moteur ECM AVERTISSEMENT L’extérieur de l’unité doit posséder une mise à la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un problème électrique se produisait.
  • Page 29 All manuals and user guides at all-guides.com Pour assurer un fonctionnement sécuritaire et INSTALLATION DU BRÛLEUR satisfaisant, les appareils fonctionnant au mazout devraient toujours être raccordés à des tuyaux dont AVERTISSEMENT le tirage est suffisant ou à un système d’évacuation mural approuvé.
  • Page 30 All manuals and user guides at all-guides.com L’appareil chauffage central nécessite approvisionnement adéquat en air de combustion. Il DISPOSITIF D'ARRÊT est fréquent de considérer que les vieilles maisons comportent suffisamment d’infiltrations d’air pour ANTI-REFOULEMENT (BVSO) combler les besoins en air de combustion de POUR ÉVACUATION PAR CHEMINÉE l’appareil de chauffage central.
  • Page 31 All manuals and user guides at all-guides.com 2.9.1 Système de filtration de l’air 2.7.2 Brûleur - Air de combustion extérieur Un filtre à air de type et de dimension appropriés doit Certains brûleurs sont conçus pour permettre un apport en obligatoirement être installé...
  • Page 32 All manuals and user guides at all-guides.com Figure 5:Délais d'arrêt du ventilateur-Carte # ST9103A Table 5: Ajustement CFM - Tous les modes SW3 – ADJ (Ajustement) Chauffage Climatisation Position interrupteurs augmentation augmentation ou réduction ou réduction POSITION +10% +10% -10% -10% Figure 6: Délais de départ et d'arrêt du ventilateur-Carte # 1158...
  • Page 33 All manuals and user guides at all-guides.com 2.12.3 Unité de climatisation SÉQUENCE DE (ou Thermopompe) FONCTIONNEMENT EN MODE CHAUFFAGE AU MAZOUT Un serpentin pour la climatisation doit être installé sur Le contact W - R du thermostat ferme ; l’alimentation d’air chaud seulement. MISE EN GARDE Le moteur du brûleur démarre pour faire un conditionnement de la chambre de...
  • Page 34 All manuals and user guides at all-guides.com 3.3.3 Vérification de la combustion 3.3.5 Test de pression dessus feu La pression au-dessus de la flamme, mesurée à la AVERTISSEMENT fenêtre d'observation (située au centre, au dessus Les surfaces métalliques de l’échangeur peuvent contenir du brûleur, dans le panneau avant de l'appareil de de l’huile et l’isolation des déflecteurs contient des liants.
  • Page 35 All manuals and user guides at all-guides.com température corresponde à celle des Avant d’appeler pour un service de réparation, spécifications. Si la hausse de température vérifier les points suivants : excessive semble irrémédiable, s’assurer qu’il n’y a Vérifier le niveau de mazout du réservoir et si le pas de restrictions dans les conduits, un filtre à...
  • Page 36 All manuals and user guides at all-guides.com NETTOYAGE DU DISPOSITIF D’ARRÊT REMPLACEMENT DU FILTRE ANTI-REFOULEMENT (BVSO) À AIR Pour un fonctionnement continu et sûr, le dispositif d’arrêt doit Des filtres sales ont une incidence sur l’efficacité de être inspecté et entretenu chaque année par un technicien l’appareil de chauffage central et augmentent la qualifié.
  • Page 37 All manuals and user guides at all-guides.com 5 Fiche technique de l'appareil Modèle : Numéro de série : Date d’installation de la fournaise : Nos tél. service – Jour : Soir : Nom et adresse du technicien de service : RÉSULTAT DU TEST DE MISE EN MARCHE Gicleur : Pression :...
  • Page 38 All manuals and user guides at all-guides.com Table 7: Spécifications techniques UNITÉ AVEC MOTEUR 1/3 HP PSC UNITÉ AVEC M OTEUR 1/2 HP ECM TAUX ET PERFORMANCE Allure de chauffe (USGPH)* 0.55 0.70 0.55 0.70 Input (BTU/h)* 77,000 98,000 77,000 98,000 Puissance de chauffage maximum (BTU/h)* 66,000...
  • Page 39 All manuals and user guides at all-guides.com Table 8: Débit d'air, unité avec moteur 1/2 HP ECM MODE DE CHAUFFAGE AU MAZOUT Signal 24 VAC (R) sur W seulement SW1- Chauffage PCM avec interrupteur PCM avec interrupteur DIP PCM avec interrupteur DIP Puissance Chauffage Position DIP "SW3-ADJ",...
  • Page 40 All manuals and user guides at all-guides.com Table 9: Débit d'air (PCM), unité avec moteur 1/3 HP AM T098 PRESS ION STATIQ UE EXTERNE AVE C FILTRE À AIR VITE SSE 0.2" (W .C.) 0.3" (W .C.) 0 .4" (W .C.) 0.5"...
  • Page 41 All manuals and user guides at all-guides.com Figure 7: Dimensions de la fournaise...
  • Page 42 All manuals and user guides at all-guides.com Figure 8: Diagramme électrique - Moteur 4 vitesses (PSC) ____________________________________________________________________________________...
  • Page 43 All manuals and user guides at all-guides.com Figure 9: Diagramme électrique - Moteur vitesse variable (ECM)
  • Page 44 All manuals and user guides at all-guides.com COMPOSANTES PIÈCES DE REMPLACEMENT ____________________________________________________________________________________...
  • Page 45 All manuals and user guides at all-guides.com Figure 10: Liste de pièces - Avec moteur 4 vitesses (PSC) B50082E...
  • Page 46 All manuals and user guides at all-guides.com Table 11: Liste de pièces - Avec moteur (PSC) ITEM No DESS DESCRIPTION COMMENTAIRES B03540 ASS ECHANGEUR CHALEUR Échangeur seul J06L002 JOINT EXTRUDE 1/4 X 1/8 X 25' B03570 ASS. PLANCHER B03561 CACHE FIL INT B03572 ASS SEPARATEUR BAS Comprend panneau, 3 bandes scellantes et déflecteur...
  • Page 47 All manuals and user guides at all-guides.com Figure 11: Liste de pièces - Avec moteur vitesse variable (ECM) B50083E...
  • Page 48 All manuals and user guides at all-guides.com Table 12:Liste de pièces - Avec moteur vitesse variable (ECM) ITEM No DESS DESCRIPTION COMMENTAIRES B03540 ASS ECHANGEUR CHALEUR Échangeur seul J06L002 JOINT EXTRUDE 1/4 X 1/8 X 25' B03570 ASS. PLANCHER B03561 CACHE FIL INT B03572 ASS SEPARATEUR BAS...

Ce manuel est également adapté pour:

Amt098sdAmt098sv