3.10 Exhaust gas loss

Calculation of the exhaust gas loss with heating oil EL according
to BImSchV dated 1.10.1988
q
= (t
- tL) x ((A
/ CO
) + B)
A
A
1
2
Given:
q
= Exhaust gas loss in %
A
t
= Exhaust gas temperature in °C
A
t
= Combustion air temperature in °C
L
CO
= Volumetric content of carbon dioxide in the dry
2
exhaust gas in %
A
= Factor for natural gas = 0,37
1
B
= Factor for natural gas = 0,009
Example:
Exhaust gas temperature
Combustion air temperature
Carbon dioxide content
q
= (169 - 18) x ((0,37 / 9,5) + 0,009) = 7,240 %
A
Exhaust gas loss
t
= 169°C
A
t
= 18°C
L
CO
= 9,5 %
2
q
= 7,2 %
A
3.10 Pertes de fumées
Le calcul des pertes de fumées pour le fioul EL se fait d'après
BImSchV du 1.10.1988:
q
= (t
- tL) x ((A
/ CO
) + B)
A
A
1
2
Ce qui signifie:
q
= Pertes de fumées en %
A
t
= Température des fumées en °C
A
t
= Température de l'air de combustion en °C
L
CO
= Teneur volumétrique en dioxyde de carbone dans les
2
fumées sèches en %
A
= Facteur du gaz naturel = 0,37
1
B
= Facteur du gaz naturel = 0,009
Exemple:
Température des fumées
Température de l'air de combustion
Teneur en dioxyde de carbone
q
= (169 - 18) x ((0,37 / 9,5) + 0,009) = 7,240 %
A
Pertes de fumées
19
t
= 169°C
A
t
= 18°C
L
CO
= 12,5 %
2
q
= 7,2 %
A