D. PROTOCOLE BACNET IP
Les objets suivants sont accessibles en BACnet IP :
Variables BACnet IP
PROPRIÉTÉ
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Location
Firmware_Revision
Application_Software_Version
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported DEVICE, ANALOG_VALUE, POSITIVE_INTEGER_VALUE
Object_List [17]
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Device_Address_Binding
Database_Revision
Serial_Number
R: Read Property, W: Write Property, -E: Enregistré en mémoire permanente
Analog value Object 0
PROPRIÉTÉ
Object_Identifier
Object_Name
Object_Type
Description
Present_Value
Status_Flags
Event_State
Out_Of_Service
Units
R: Read Property, W: Write Property, -E: Enregistré en mémoire permanente
© 2019 SLAT Sous réserve de modifications
SYNAPS
Instance du produit, par défaut : 421000
Identification du SYNAPS (16 caractères max.). Par défaut : ""
DEVICE (8)
OPERATIONAL (0) ou STATUS_NON_OPERATIONAL (4) si non prêt
"SLAT"
954
Type du produit
Emplacement du produit (32 caractères max.). Par défaut : ""
Version du Firmware de communication
""
1
12
read-property, write-property, who-has, who-is, device-communication control
device, analog-value 0 ...10, positive_integer_value 0...4
1476
NO_SEGMENTATION (3)
3000
3
-
0
Numéro de série
ANALOG VALUE OBJECT 0
analog-value 0
"Vout"
ANALOG_VALUE (2)
"Output Voltage"
Tension de sortie
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
NORMAL (0)
FALSE (0)
Volts (5)
REMARQUE / VALEUR
REMARQUE / VALEUR
28
MANUEL D'UTILISATION
RW
RW-E
RW-E
R
R
R
R
R
RW-E
R
R
R
R
R
R
R
R
R
R
R
R
R
R
RW
R
R
R
R
R
R
R
R
R
MAN802210067_FR