SERVICE AND REPAIR
All work on the regulator is to carry out only in the pressure-
free condition. The safety regulations, in particular the
UVV's, as well as the DVGW papers G 491 and G 495 are to
be considered:
» Valves on the upstream- and downstream side are to
close.
» The pressure must be reduced by the relief valve on the
outlet side, up to zero level
ADJUSTING TOOL
SSV 022, funktion
SSV 022, funktion
1) For special version SSV 022-1, the function of pdsu (lower shut-off) isn't existent!
SSV POSITION INDICATOR (OPTION)
Plug
SSV position indicator for assembly* at the reset shaft,
*order technical information No. 142-099-6001
pdso
1
pdsu
Initiator
CAUTION
Before disassembling the SSV, the loading
spring has to be released fully!
-> Adjusting tool a/f 13 (Hexagon)
-> Screw-driver, No. 2
a/f 13 Hexagon
Reset shaft