CB 230 RTS
Reflex photoelectric cell
• Wiring to "Cell active during closing input" with autotest - Fig. 15
230V orange light - Fig. 16
Aerial - Fig. 17
Keyswitch - Fig. 19
Video doorphones - Fig. 20
7 - ADVANCED PARAMETER SETTING
The change in dipswitch status is taken into account immediately.
7.1 Torques for motors 1 and 2 - Dipswitches 1 to 4
DIP - SW 1
OFF
Motor 1 torque
OFF
setting
ON
ON
DIP - SW 3
OFF
Motor 2 torque
OFF
setting
ON
ON
7.2 Gate leaf mode 1 - Dipswitch 5
DIP - SW 5
Setting
OFF
Both motors operating
ON
One motor only operating
Power is not supplied to the output M2.
All operating modes cane be used.
7.3 Offset of the gate leaves during closing - Dipswitch 6
DIP - SW 6
Setting
OFF
opening, set during programming
ON
7.4 Operating modes - Dipswitches 7 to 9
DIP -
DIP -
DIP -
Setting
SW 7
SW 8
SW 9
Sequential
OFF
OFF
OFF
Each press on the remote control button causes the
etc.
Sequential + automatic timed close
OFF
OFF
ON
Operation in automatic closing mode is only
In sequential mode with automatic timed close:
-
programmed with the TIME potentiometer,
- pressing a button on the remote control interrupts
the movement taking place and the timed close
5
DIP - SW 2
Setting
OFF
100% torque
ON
75% torque
OFF
50% torque
ON
25% torque
DIP - SW 4
Setting
OFF
100% torque
ON
75% torque
OFF
50% torque
ON
25% torque
Semi-automatic
OFF
ON
OFF
In semi-automatic mode, the gate is always closed
or open:
- pressing a button on the remote control during
- pressing a button on the remote control during closing
causes it to reopen.
Automatic
OFF
ON
ON
always be the closed position.
Operation in automatic closing mode is only
-
programmed with the TIME potentiometer,
- pressing a button on the remote control during
- pressing a button on the remote control during
closing causes it to reopen,
- pressing a button on the remote control during the
the gate will not close. It will close once the obstacle
is removed.
Automatic + cell blocking
ON
OFF
OFF
always be the closed position.
Operation in automatic closing mode is only
programmed in with the TIME potentiometer.
the gate will not close. It will close once the obstacle
is removed.
Deadman's wired control
ON
ON
ON
The gate can only be controlled by continuous action
on a wired control: opening on OPENING control
input, closing on CLOSURE control input,
The pedestrian and radio controls are inactive.
There is no slowdown zone when the deadman's
wired control is operating,
This operating mode can be activated without
programming.
7.5 Lock release - Dipswitch 10
DIP - SW 10
Setting
OFF
Without lock release
ON
gentle push in the closing direction.
7.6 Orange light warning - Dipswitch 11
DIP - SW 11
Setting
OFF
Without warning
ON
With 2 s warning prior to movement
7.7 Cell autotest when closing - Dipswitch 12
DIP - SW 12
Setting
OFF
Without autotest
ON
connected to the cell active during closing input.