Note: Do not use stranded wires, only solid wires
or stranded wires with ferrules!
3
Notes
The local regulations for electrical installations must be complied with
If the reference room is equipped with thermostatic radiator valves, they
must be set to their fully open position
If you wish to check the radio link, press the TEST button at the rear of
the REV24RF..
LED_1 is lit red if the RCR10/868 receives very weak or corrupted
control telegrams, or no control telegrams at all for about 65 minutes. In
this case, check the display of the REV24RF.. to see if there is an error
message
As long as the RCR10/868 receives control telegrams, the receiver
works normally. If a control telegram is not correctly received, the relay
will maintain the position assumed last.
Commissioning RF set
1
Switching on the REV24RF..
Remove the black battery transit tab (Fig. F); as soon as the tab is
removed, the unit is ready to operate
2
Selecting the language
When starting up, the display shows the type of controller at top left and
"THANK YOU ..." in all available languages on the text line
Press one of the buttons to stop the running display. The choice of
languages starts with "ENGLISH" (factory setting). Press
until the language you require appears. Press
confirm the selected language (also refer to Fig. G)
3
Mounting the RCR10/868 temporarily
If possible, mount the receiver temporarily (e.g. using double-sided
adhesive tape), thus allowing you to find the location with the best
reception conditions
Wire completely the RCR10/868.
For steps to be followed, refer to Figs. H through M (close the front also)
4
RCR10/868 and REV24RF..
The units are supplied interconnected
For manual connection, refer to operating instructions
5
Mounting and setting up the
REV24RF..
Refer to "Mounting instructions REV24RF.. and RCR10/868"
Mount or set up the REV24RF.. at your preferred location:
Remove the unit from its baseplate; for procedure, refer to Fig. A
- For wall mounting, refer to Figs. B, C and D
- For setting up, refer to Fig. E
Configuration and function check REV24RF..
1

Configuration

1.1

DIP switches

ON /
OFF
Sensor calibration on
See 1.1.1
Sensor calibration off
Setpoint limitation 16...35 °C
1.1.2
Setpoint limitation 3...35 °C
Temperature display °F
1.1.3
Temperature display °C
PID self-learning
PID 6
1.1.4
PID12
2-Point
1.1.9
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button (also refer to Fig.
8). Otherwise, the previous settings will be maintained!
CE1G2206xx
or
or move the slider to
1
2
3
4
5
DIP switch reset
Note: The factory setting of all DIP switches is
19.02.2008
As soon as the RCR10/868 receives another correct control telegram
from the REV24RF.., the receiver continues to work normally
If, for 60 minutes, the RCR10/868 receives no control telegram, or no
correct control telegram, the relay will be deenergized. Hence, the
controlled device is switched off. LED_1 is lit red.
As soon as the RCR10/868 receives another correct control telegram
from the REV24RF.., the receiver continues to work normally
In the event of a power failure at the RCR10/868, the relay is switched
OFF
Should the REV24RF.. become faulty, the relay of the RCR10/868 can
be controlled manually. As soon as the REV24RF.. resumes correct
operation, its control telegrams will overwrite the relay's manual control.
This process can take up to 130 minutes
Press override button
relay. LED_1 indicates manual control by blinking at high frequency.
LED_2 is lit when Lx-L1 is closed (Lx-L2 open). LED_2 is dark when
Lx-L1 is open (Lx-L2 closed)
6
Finding the best place for reception
a)
Switch on the RCR10/868
b)
Set up the REV24RF.. at your preferred location.
Test the radio link by pressing the TEST button at the rear of the
controller (refer to Fig. N1)
c)
The display of the REV24RF.. shows the quality of the radio link. The
longer the bar below the numbers 0...9, the better the quality of the radio
link. If the bar only appears below number 0, there is no secure radio link
(refer to operating instructions)
Insufficient
Sufficient
d)
On the receiver, LED_1 indicates the quality of the radio link (refer to Fig.
N2):
Red = insufficient or no connection
Orange
= good
Green
= very good
e)
If the quality of the radio link is insufficient, reduce the distance between
controller and receiver.
Then, repeat the test
7
Mounting the RCR10/868 in its final
place
a)
Switch power off
b)
Mark the place where the RCR10/868 is located
c)
If necessary, remove wiring
d)
Mount the receiver at the place previously identified (refer to
H through M), complete wiring and close the housing
e)
Switch power on
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
OFF
to manually energize and deenergize the
Good
Very good
Periodic pump run on
Periodic pump run off
Optimum start control:1 h/°C
Optimum start control: ¼ h/°C
Optimum start control: ½ h/°C
Optimum start control: Off
(Cooling on)
(Heating on)
Quartz
Radio clock
Figs.
See
1.1.5
1.1.6
1.1.7
1.1.8
1.1.9
7/48