Before performing any type of operation, make sure that the automation is turned off and the batteries are disconnected.
Start-up and adjustment must be performed in the following order when the automation is installed:
1. Connect the accessories, opening and safety sensors, blocking device, batteries and selector.
2. Jumper the safety contacts 1-2, 1-3, 1-4, 8-9, 8-11 on the control panel and 1-5 on plus module DAS902MP, if not used.
3. Connect the mains power supply to the automation.
4. Set the following parameters:
PARAMETER
05
Lock configuration (main control unit)
06
Lock release
09
Central presence sensor test
10
Emergency Unit Monitoring (00÷02)
12
Selection of opening direction
16
Inner Impulse (motion) Monitoring
29
Side presence sensor test
36
Emergency Action (00÷01)
44
Exit Lock (00÷01)
53
Operator Type (00÷04)
67
Selection of the type of automation
68
Door weight (00÷40kg x10)
98
Lock Configuration, terminal 16-17 - DAS902MP
Function Select, terminal 6 - DAS902MP
99
Operation mode selector key lock
B1
(for COM500ER,COM501ES/ER,COM502ES)
If the CT Configuration Tool is used, disable the "learn access":
MMI Write access
MMI Read access
DESCRIPTION
Learn Access
NOTE: Set ONLY if installed bistable lock DAS802LOKB= 12.
10= No lock.
11= Antipanic lock (LDP).
12= Bi-stable lock (LDB)
.
00= Off.
01= On.
On DAS200RF and DAS200TRF set 01
00= None ( factory setting).
01= Presence sensor 1 (set if a presence sensor with monitoring is installed).
02= Presence sensor 1 and 2 (set if two presence sensors with monitoring are installed).
00= Off.
01= Convenience monitoring.
02= Redundant monitoring.
On DAS200RF and DAS200TRF set 02.
00= Right hand opening for single door wing automation.
01= Left hand opening for single door wing automation and for double door automation
(factory setting).
According to EN16005 it is a demand to have Inner impulse monitoring= 01 in escape
routes.
00= Disables monitoring.
01= Enables monitoring.
On DAS200RF and DAS200TRF set 01
00= None (factory setting).
01= Presence sensor 1 (set if a presence sensor with monitoring is installed).
02= Presence sensor 1 and 2 (set if two presence sensors with monitoring are installed).
00= Closing.
01= Opening.
On DAS200RF and DAS200TRF set 01.
00= Off.
01= On.
On DAS200RF and DAS200TRF set 00
00= Slider.
01/02/03= DO NOT USE.
04 = Mechanical Emergency Unit Slider.
On DAS200RF and DAS200TRF set 04.
00= Automation with one door wing
01= Automation with two door wings
The weight of the door is not automatically learned on the DAS200RF and DAS200TRF
it must be set manually
.
On DAS200TRF set the weight of the fast wing only (2 wings in the case of a 2 + 2
operator).
Set ONLY if installed bistable lock DAS802LOKB.
11= Bistable lock.
00= No function.
01= Sustainable disable.
02= Enable the Mode Selector with a key (only COM500ER).
Set 02, ONLY if installed a COM500ER program selector.
00= No access code ( do not use for escape route)
01= Hold for two sec.( do not use for escape route)
02= Passcode. ( to use with COM501ES and COM502ES)
03= Key (to use with COM501ER)
7