Nordica Giada Instructions Pour L'installation, L'utilisation Et L'entretien page 20

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

50 cm
2 m
1
m
CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the
roof
α α α α
15°
30°
45°
60°
20
10 m
(1) The chimney cap must not show hindrances within 10 m from
walls, pitches and trees. Otherwise raise it of at least 1 m over the
hindrance.
The chimney cap must exceed the ridge of the roof of at least 1 m.
>A
H min.
(1)Ridge axis
α
Distance between the roof
ridge and the stack
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
(1) In case of flues side by side, a chimney cap must be higher
than the other one of at least 50 cm in order to avoid pressure
transfers between the flues themselves.
> _ A
0,5 m
(2)Roof
Minimum height of the stack
(measured from the outlet)
0.50 m above the roof ridge
1.00 m from the roof
0.50 m above the roof ridge
1.30 m from the roof
0.50 m above the roof ridge
2.00 m from the roof
0.50 m above the roof ridge
2.60 m from the roof
UNI 10683/98
H (m)
7196001 Rev.05 – EN
GIADA
Picture 5
Picture 6
Picture 7

Publicité

Table des Matières
loading

Table des Matières