Atlas Copco QAS 150 Fd S5 Manuel D'instructions page 228

Table des Matières
Coolat heater
1
2
3
A
B
C
A
B
C
450
c6
8
1
2
451
c0
PE
b54
PE
b54
451
b0
5
450
b6
20
21
22
23
NOTES
Note 3: With "N- EDF", do NOT connect (N) to (PE).T22/23 is to be mounted on the (PE) conductor, between PE terminal and PE cooper bar.
Note 4: Remove link "M" when parallelling with the mains. When parallelling multiple gen-sets in ISLAND-mode, link "M" is necessary.
Note 5: Remove link "P" when NOT running in ISLAND-mode. See table 9 for the setting of "P" link and the status of terminals X25.10, X25.11 and
X25.12 with the differents application modes.
O7 - Battery charger
BUS voltage
3
5
66
67
68
69
-
+
12V
1
P
E
N
L
1
PE
N
L1
33
34
35
36
6
3
4
5
M
M
M
PE N
L
M
230V
O22 - ZBP
connector
5
1
2
1
2
9
10
11
12
13
14
15
16
P
REMOTE
START
- 228 -
POSITION OF RELAY CONTACTS
K0
K1
K2
07.C1
07.B2
07.B2
K8
K9
K11
02.C2
04.C9
02.C9
04.D6
05.F10
K15
K23
K24
05.D4
07.B8
07.B9
K29
K40
07.B7
03.A9
POSITION OF SWITCH CONTACTS
S1
S2
S3
07.C1
07.C3
S5
S6
S9
02.B5
07.F10
02.D7
03.B1
05.E10
S12
S11
S15
02.D5
02.D6
02.C8
05.B3
03.B2
05.F2
06.B3
S23
3
4
5
PE
05.F8
Table 9 - CONNECTOR X25 - 10/11/12 STATUS
WITH MB
APPLICATION
10-11
(Open)
Island
AMF
NO Contact
NO Contact
Peak Shaving
NO Contact
NO Contact
Fixed Power
NO Contact
NO Contact
Load Take Over
NO Contact
NO Contact
Mains Power Exp/Imp
NO Contact
NO Contact
K3
K7
02.E3
02.E3
02.C6
K12
K14
04.D7
05.D5
K27
K28
03.D8
07.B7
S4
02.B2
07.C3
05.F10
S10
02.C1
S22
05.E7
WITHOUT MB
10-12
10-11
10-12
(Close)
(Open)
(Close)
Link P
Link P
Link P
Link P