California Proposition 65 Warning - Pentair MYERS DE Série Instructions D'utilisation

Masquer les pouces Voir aussi pour MYERS DE Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation
Pump normally runs hot. To avoid burns when servicing
pump, allow it to cool for 20 minutes after shut-down
before handling it.
Do not run pump dry. Dry running can overheat pump
and will void warranty.
Pump is permanently lubricated. No oiling or greasing
is required in normal operation. For overhaul, see
instructions under "Service".
Not for use with salt water or brine.
Hazardous voltage. Can shock, burn, or
cause death.
During operation the pump is in water. To avoid fatal
shocks, proceed as follows if pump needs servicing:
A. Ground pump according to all applicable codes and
ordinances.
B. Disconnect power to outlet box or circuit breaker
before servicing.
C. To reduce risk of electric shock, take care when
changing fuses or resetting circuit breaker. Do not
stand in water when working on control box or with
circuit breaker.
Single Phase Pumps:
D. When using cord and plug, plug into a grounded
outlet only. When wiring to a system control, connect
pump ground lead to system ground.
Three Phase Pumps:
Risk of electrical shock. Do not remove
cord and strain relief. Do not connect conduit to
pump.
E. Three phase pumps are intended for permanent
connection only. Provide strain relief at control box
for power supply cord connection to box. All control
components must be UL listed and suitable for end
use application. Only qualified personnel should
install the pump and associated control equipment.

California Proposition 65 Warning

This product and related accessories contain
chemicals known to the State of California to cause
cancer, birth defects or other reproductive harm.
PERFORMANCE
Model
5'
DE40PC1
92
DE50PC1
97
DSW40P1
103
DSW50P1
114
DSW50M2
114
DSW100M2
145
GPM of Water at Total Feet of Head
10'
15'
20'
80
66
53
83
69
56
79
58
39
88
67
47
88
67
47
130
110
90
INSTALLATION
Risk of electrical shock. Can burn or kill.
Do not lift pump by power cord. See "Lifting Pump" and
Figure 1.
For 3-phase installation and rotation, See "Electrical,"
Page 4.
NOTE: Install pump on a hard, level surface (cement,
asphalt, etc.). Never place pump directly on earth, clay, or
gravel surfaces. Basin must be at least 18" in diameter and
30" deep.
Risk of electrical shock. Can burn or kill.
Do not lift pump by power cord.
Figure 1
Lifting Pump
1. Use handle on top of pump for all lifting/lowering of
pump. Disconnect power to pump before doing any
work on pump or attempting to remove pump from
sump.
2. Attempting to lift or support pump by power cord can
damage cord and cord connections.
3. Cord may pull apart, exposing bare wires with
possibility of fire or electrical shock.
4. Lifting or supporting pump by power cord will void
warranty.
25'
30'
38
19
42
25
20
26
26
71
50
4701 0904
35'
40'
Shut off
33 ft.
5
36 ft.
27 ft.
30 ft.
30 ft.
12
36 ft.
3

Publicité

Table des Matières
loading

Table des Matières