9 Technical data
Product characteristics
Fail-safe inductive sensor
Metal thread M12 x 1
M12 connector
Enable zone 0.5...4 mm; [nf] non-flush mountable
Complies with the requirements:
EN ISO 13849-1: 2015 category 2 PL d (can be used in applications up to cat. 3)
IEC 61508: SIL 2
IEC 62061: SILcl 2
Application
Type of operation
Electrical data
Electrical design
Operating voltage
Rated insulation voltage
Current consumption
Protection class
Reverse polarity protection
Outputs
Output function
Output data
Output voltage at 24 V
Voltage drop
Current rating
Short-circuit protection
Max. capacitive load CL_max
Range
Enable zone
Safe switching off distance s(ar)
Reaction times
Power-on delay time
Response time to safety request
Response time when approaching
the enable zone (enable time)
Risk time (response time for safety
-related faults)
12
[V]
[V]
[mA]
[V]
[mA]
[nF]
[mm]
[mm]
[s]
[ms]
[ms]
[ms]
continuous operation (maintenance-free)
DC PNP
24 DC (19.2...30 DC)
30
< 20
III
yes
2 x OSSD (A1 and A2)
Interface type C class 1
compatible with EN 61131-2 inputs type 1, 2
< 2.5; (30 mA)
100
yes
20
0.5...4
6
1
≤ 1
≤ 1
≤ 20
Inductive sensors
Seite 1 von 2

Publicité