The control unit with microcontroller for RI.5K is suitable for motors with up to 500W power.
The "Adjustment of the motor torque" can be carried out using the 5-position "POWER" switch.
This switch should be placed in the position in which, once the automation has started, it can be stopped
if it comes up against a certain amount of resistance. This acts as a safety function to protect people or
things from impact.
The "Starting function" allows the maximum motor torque to be obtained for about 1 second when the
motor is started. This starting function can be deactivated by positioning the DSW5 Dip-Switch on OFF.
Installation instructions.
a)
The electrical installation and functioning logic must comply with current standards.
b)
Keep the power cables (for the motor and power supply) away from the control cables (buttons,
photocells, radio). To avoid interference use two separate sheaths (see EN 60204-1 15.1.3).
c)
Check all the connections again before supplying voltage.
d)
Check that the Dip-Switch settings are as required.
e)
When voltage is supplied, the "POWER" led should light up. If this is not the case, check the state
of the fuses and whether 230 Vac 50 Hz power is present between terminals 1 and 2 (INPUT 230VAC
- respect phase/neutral wire position).
f)
The N.C. inputs not used must be connected to the common "+V".
g)
If the direction of the motor rotation is not correct, invert the "OPEN" - "CLOSE" wires of the motor
as well as the wires of the "FCA" - "FCC" limit switches.
Input/Output functions
(1,2)
INPUT 230VAC= Control unit 230Vac 50 Hz power supply
(3,4,5)
COM/APRE/CHIUDE= Connection to the corresponding 230Vac 50 Hz motor terminals
(6,7)
LAMP230= Connection to the 230Vac blinker.
(8,9)
OUT 24VAC= 24Vac auxiliary power supply output (1A max.).
(10,11) SCA= "Gate open warning light" contact
(12,13) +V= Common connection to all the control inputs.
(14)
FTC= Photocell receiver input (n.c. contact).
(15)
FCA= Limit switch input - Opening (n.c. contact).
(16)
FCC= Limit switch input - Closing (n.c. contact).
(17)
STOP= STOP button input (n.c. contact).
(18)
P.P.= STEP-by-STEP button input (n.o. contact).
(19)
APRE= OPEN button input (n.o. contact).
(20)
CHIUDE= CLOSE button input (n.o. contact).
(21,22) ANT.= Input of radio board antenna
(23,24) RX 2CH.= Radio board 2nd channel contact (n.o. contact).
6
Control unit with microcontroller for RI.5K
(respect phase/neutral wire position).
(the earth wire (green/yellow) must be connected to the motor housing).