Télécharger Imprimer la page

Carrier 80AW9025 Manuel D'installation page 8

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
Application scheme
See fig. 1
1.
Hydronic module (80AWX / 80AWH)
2.
2 zone kit (80AW9025)
3.
zone 1 water connections (ball valves: field supplied)
4.
zone 2 water connections (ball valves: field supplied)
5.
zone 1 collectors
6.
zone 2 collectors
T1, T2, T3: zone 1 terminals
C1, C2, C3, C4, C5, C6: thermostats connected to terminals
CA: user interface (additional or shifted from hydronic
module) or sensor or thermostat connected to 2 zone kit;
placed in zone 1
CB: user interface (additional or shifted from hydronic
module) or sensor or thermostat connected to 2 zone kit;
placed in zone 2
Terminals
Terminals can be of the following types:
floor circuit
fan coils
radiators
low temperature radiators
Different terminals have different water temperature
requirements.
2 zone kit allows to use, at the same time, terminals with
different water temperature requirements.
Unit description
See fig. 3
1.
TW1 water temperature sensor
2.
Water pump (zone 1)
3.
3 way valve and actuator (zone 1)
4.
Collector
5.
TWB2 water temperature sensor
Box content
See fig. 4
1.
2 zone kit
2.
2 zone kit installation manual
80AW9025
8
All manuals and user guides at all-guides.com
Room temperature control
Different terminals (T1, T2...Tn) can be placed in a single
room or in multiple rooms.
Each of them can have a thermostat, to stop the terminal
when a certain temperature is reached.
It is possible to control up to 2 rooms (placed in different
zones), with a user interface or a thermostat connected to
the unit.
In each zone, the controlled room should be the one with
the highest heating/cooling requirements.
In this room it is not required to place a thermostat on the
terminal/s.
It is suggested to place a thermostat on terminals placed in
rooms with significantly different thermal requirements.
In one zone, a room sensor (33AW-RRS01) can be used
instead of a user interface.
If a sensor is used, in that zone humidity information and
temporary setpoint override are not available
It is recommended to control the room with the user
interface, or at least with a room sensor; this way the control
adjusts water temperature to meet the setpoint and comfort
and energy efficiency are optimized.
If no user interface/room sensor is used:
if thermostats are used, set climatic curves slightly higher
in heat mode and slightly lower in cool mode.
if no thermostats are used (temperature requirements
should be similar for all rooms), climatic curves must be
set exactly right for both heating and cooling operation.
6.
Pressure switch
7.
Drain valve
8.
Water pump (zone 2)
9.
Control box
10.
Electronic board
11.
Terminal block

Publicité

loading