Sabiana Energy Smart ENY SHP-130 Instructions D'installation, D'utilisation Et D'entretien page 111

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLER MAINTENANCE
The following maintenance interventions must
only be carried out by the installer or by qualified
personnel:
• Inspect the filters and clean them if necessary;
• Inspect the heat exchanger and clean it if nec-
essary;
• Inspect the fans and clean them if necessary;
• Check the condensate drain once every two
years.
The following paragraphs have a short descrip-
tion of the maintenance interventions.
PLEASE NOTE: If maintenance is not carried out
regularly, the ventilation system might not work
properly.
• Check the heat exchanger
Always disconnect the power
before accessing the unit.
Check the heat exchanger once every two years.
• Use a screwdriver with TORX head to remove the
heat exchanger panel cover.
ATTENTION!: once the screws "1" are removed,
support the panel "2" in the way that it does not fall
down.
• Remove the support brackets "A" using a screw-
driver.
• Extract the heat exchanger (B)
ATTENTION!: The heat exchanger may contain
residual water.
• Inspect the condition of the heat exchanger and
clean it if necessary:
- Use a soft brush to clean the fins.
- Use a vacuum cleaner or compressor (not high
pressure) to remove debris and dust.
IMPORTANT!: Always clean in the opposite di-
rection of the air flow.
- If no other operation is necessary, put all the
components back in, in the opposite order and
reconnect the power.
1
1
2
1
1
English
B
A
111

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Energy smart eny shp-150

Table des Matières