Mounting
Intended use
The input/output module has two inputs/outputs and is
operated on the FDnet/C-NET. The inputs/outputs can be
connected as follows:
– Collective detector lines and conventional detector lines
– Control line
– Contact input
Housing FDCH221 is available to protect the module from
environmental influences like moisture and humidity.
Mounting the input/output module
The input/output module can be mounted as follows:
– In a fire control panel using the mounting feet supplied
on a U-rail TS35 (Fig. 1)
– In a housing FDCH221 available as an accessory
(Fig. 2...4)
Mounting the input/output module in a fire control
panel on a DIN rail
NOTICE
High temperatures in the module's
environment
Module overheating and damage
·
A minimum clearance of 1 cm must be
observed between two modules or between
the module and any other boundary.
1. Insert two mounting feet into the input/output module.
2. Push the input/output module with the mounting feet
against the DIN rail until the mounting feet engage
(Fig. 1).
Mounting in housing FDCH221
NOTICE
Module use in a damp, wet or dusty
environment
Damage to module from dust or jet of water
·
In damp, wet or dusty environments, fit the
module in a housing FDCH221.
1. Open housing (Fig. 4).
2. Determine cable entries in housing and break them
open.
3. Use two screws to fit the housing on a plane surface
(Fig. 2).
4. Secure the M20 x 1.5 cable glands on the housing and
guide in the cables (Fig. 3).
5. Use two M3 x 12 screws to mount the module in the
housing.
6. Close housing using supplied screws (Fig. 4).
Building Technologies
Fire Safety
All manuals and user guides at all-guides.com
Electrical connection
1. Connect the cables to the terminals according to the pin
2. Fuse the DC 24 V external supply with a fuse (3) of
3. For currents up to max. 0.7 A, use the internal fuses (1)
4. Connect the monitoring resistors or end-of-lines (EOL).
5. Fix the cables to the input/output module using cable
assignment (Fig. 10). Only connect one wire per
terminal.
max. 2 AT.
The currents for both control lines are supplied by
means of the DC 24 V external supply.
or fuse the control line subject to the number of outputs
used with an external fuse (2) of max. 1 AT or 1.5 AT:
1x 1.5 AT or 2x 1 AT (T
amb
The internal fuses (1) are activated when delivered. Max.
permissible current: 0.7 A.
The jumpers are not connected.
These must be connected at the end of the line
(Fig. 5 ...9)!
ties (max. width 2.6 mm).
You will find more information in document 009122.
< 60 °C)
009124_k_--_--
2018-07-06
3