Télécharger Imprimer la page

Victron energy EasySolar 12/1600/70 Manuel D'instructions page 22

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5.5.3 Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP
switches of a new product are set to 'off', except for DS-2).
DS-1 Panel option
DS-2 Panel option
DS-3 Ch. voltage
DS-4 Ch. voltage
DS-5 Frequency
DS-6 Search mode
DS-7 AC-in Limit
DS-8 Store setting
Example 1: (factory setting)
1
No panel or remote
switch connected
2
No panel or remote
switch connected
3, 4
GEL 14.4V
5
Frequency: 50Hz
6
Search mode off
7
AC-in Limit 12Amp
8 Store setting: off→ on→ off
Store the settings (DS3-DS7) by changing switch ds-8 from 'off' to 'on', and then back to 'off'.
The LEDs 'charger' and 'alarm' will flash to indicate acceptance of the settings.
20
off
DS-1
on
DS-2
off
DS-3
off
DS-4
off
DS-5
off
DS-6
off
DS-7
→ ←
DS-8
Example 2
1
2
3, 4
5
6
7
8 Store setting: off→ on→ off
off
DS-1
on
DS-2
off
DS-3
on
DS-4
off
DS-5
off
DS-6
on
DS-7
→ ←
DS-8
Example 3
No panel or remote
1
switch connected
No panel or remote
2
switch connected
AGM 14,7V
3, 4
Frequency: 50Hz
5
Search mode off
6
AC-in Limit 4Amp
7
8 Store setting: off→ on→ off
on
off
on
on
on
on
off
→ ←
Panel or remote
switch connected
Panel or remote
switch connected
Tubular plate 15V
Frequency: 60Hz
Search mode on
AC-in Limit 12Amp

Publicité

loading

Ce manuel est également adapté pour:

Easysolar 24/1600/40