5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information,
please refer to the help files in the software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this range
with the AC input frequency. The output frequency is then equal to the input frequency.
Adjustability: 45 – 65Hz; 45 – 55Hz; 55 – 65Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this range with
the AC input voltage. The output voltage is then equal to the input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Inverter voltage
Output voltage of the MultiPlus in battery operation.
Adjustability: 210 – 245V
Search Mode (Applicable in stand-alone configuration only)
If search mode is 'on', the power consumption in no-load operation is decreased by approx.
70%. In this mode the Compact, when operating in inverter mode, is switched off in case of no
load or very low load and switches on every two seconds for a short period. If the output
current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut
down again.
The Search Mode can be set with a DIP switch.
The Search Mode 'shut down' and 'remain on' load levels can be set with VEConfigure.
The standard settings are:
Shut down: 40 Watt (linear load)
Turn on: 100 Watt (linear load)
14