5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please
refer to the help files in the software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
Input frequency range
Input frequency range accepted by the EasyPlus. The EasyPlus synchronises within this range with
the AC input frequency. The output frequency is then equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the EasyPlus. The EasyPlus synchronises within this range with the AC
input voltage. The output voltage is then equal to the input voltage.
Adjustability:
Lower limit: 180 - 230 V
Upper limit: 230 - 270 V
Inverter voltage
Output voltage of the EasyPlus in battery operation.
Adjustability: 210 – 245 V
Search Mode (Applicable in stand-alone configuration only)
If search mode is 'on', the power consumption in no-load operation is decreased by approx. 70 %. In
this mode the EasyPlus, when operating in inverter mode, is switched off in case of no load or very
low load, and switches on every two seconds for a short period. If the output current exceeds a set
level, the inverter will continue to operate. If not, the inverter will shut down again.
The Search Mode can be set with a DIP switch.
The Search Mode 'shut down' and 'remain on' load levels can be set with VEConfigure.
The standard settings are:
Shut down: 40 Watt (linear load)
Turn on: 100 Watt (linear load)
15