 Remote control sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote control sensor to
sense the temperature around the remote control.
Select items following the basic operation procedure
1
2
3
4
5
6
(
).
• Specify [32] for the CODE No. in Procedure
• Select the following data for the SET DATA in
4
Procedure
.
SET DATA
0000
0001
Remote control
Not used
Used
sensor
(Factory default)
When
flashes, the remote control sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote control.
 Group control
In a group control, a remote control can control up to
maximum 8 units.
• The wired remote control only can control a group
control. The wireless remote control is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "Electrical
Connection" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the indoor units by connecting the remote
control wires from the remote control terminal blocks
(A, B) of the indoor unit connected with a remote
control to the remote control terminal blocks (A, B) of
the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
21-EN
9
Test run
 Before test run
• Before turning on the power supply, carry out the
following procedure.
3
.
1) By using 500 V-megger, check that resistance
of 1 MΩ or more exists between the terminal
block L to N and the ground.
If resistance of less than 1 MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
• Do not press the electromagnetic contactor to
forcibly perform a test run. (This is very dangerous in
case the protective device does not work.)
• Before starting a test run, set addresses by following
the Installation Manual supplied with the outdoor
unit.
 Execute a test run
• When a fan operation is to be performed for an
individual indoor unit, turn off the power, short CN72
on the circuit board, and then turn the power back
on. (First set the operating mode to "fan," and then
operate.) When the test run has been performed
using this method, do NOT forget to release the
shorting of CN72 after the test run is completed.
Operate the unit with the wired remote control as usual.
For the procedure of the operation, refer to the
attached to the outdoor unit Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by turning the
thermostat - OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
– 11 –
Wired remote control
1,5
1
Push
button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
2
Push
button.
3
Select the operation mode with
button, [
Cool] or [
Heat].
• Do not run the air conditioner in a mode other
than [
Cool] or [
Heat].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
4
After the test run, push
stop a test run.
(Display part is same as procedure 1.)
5
Push
button to cancel (release from) the
test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
Wireless remote control
(TCB-AX32-UL)
2, 4
1
When TEMPORARY button is pushed for 10
seconds or more, "Pi!" sound is heard and
3
the operation changes to a forced cooling
operation. After approx. 3 minutes, a cooling
operation starts forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
TEMPORARY button
button to
22-EN