Électrovanne a réarmement manuel normalement ouvert pour gaz
Masquer les pouces Voir aussi pour M16/RMJ N.A.:

Publicité

Les langues disponibles

Les langues disponibles

3.4 - GENERIC EXAMPLE OF AN INSTALLATION
1. M16/RMJ N.A. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
external roof
10
1
4.0 - MANUAL RESET
To reset the solenoid valve:
• Make sure the valve is NOT electrically powered;
• Close the flow downstream of the solenoid valve in order to balance the pressure between upstream and downstream when
opening;
• Push the reset handgrip (9) and wait an instant to balance the pression from and to the user's up to the hooking;
• After balancing the pressures, press the reset handgrip (9) until it connects.
5.0 - FIRST START-UP
• Before start-up make sure that all of the instructions on the rating plate, including the direction of flow, are
observed;
• After having gradually pressurized the system, check the seal and operation of the solenoid valve, electrically
powering / disconnecting it.
IMPORTANT NOTE: Do not use the connector as a switch to close the solenoid valve.
• Make sure the solenoid valve is closed by electrically connecting it.
5.1 - RECOMMENDED PERIODIC CHECKS
• Use a suitable calibration tool to ensure the bolts are tightened as indicated in 3.2;
• Check tightness of the flanged/threaded connections on the system;
• Check tightness and operation of the solenoid valve;
M16/RMJ N.A.
9
8
2
6. MVS/1 relief valve
7. Pressure gauge and relative button
8. Gas detector
9. SM remote jerk ON/OFF valve lever control
10. Compensation/Vibration damping joint
internal thermal unit
3
4
5
14
Madas Technical Manual - 3|3.2bJ - REV. 0 of 1
discharge in open air
6
7
Aug 2019
st