Features

5-15R AC Outlets: Connect to 5-15P equipment plugs.
1
5-20R AC Outlets: Connect to 5-15P or 5-20P equipment plugs.
2
L5-30R AC Outlets: Connect to L5-30P equipment plugs.
3
C13 AC Outlets: Connect to C14 equipment plugs.
4
C19 AC Outlets: Connect to C20 equipment plugs.
5
UPS Source Input: Connects to a compatible outlet on the UPS system.
6
Maintenance Bypass Switch: Selects the power source that is powering the load – either the UPS source or the utility source. When the switch
7
is set to "Utility," connected equipment receives AC utility power from the PDU, but the equipment will not receive UPS battery backup power
in the event of a utility power failure. See "Manual Bypass Operation" for more information.
Diagnostic Lights (UPS Available and Maintenance Bypass Available): A green "UPS Available" light will illuminate when the UPS source
8
is connected and turned on. A yellow "Maintenance Bypass Available" light will illuminate when the utility source is connected and turned on.
Utility Source Input: Connects to the utility power source. Models PDUB15, PDUB20 and PDUB30 each have a fixed input cord and plug.
9
Model PDUBHV10 has a C14 inlet and model PDUBHV20 has a C20 inlet. Models PDUBHV10 and PDUBHV20 both include an extension
jumper and can also be used with a user-supplied power cord. (See below for a selection of compatible Tripp Lite power cords.)
UPS Connection Outlet: Connects to the UPS system's input power cord. The user must match the UPS system's input power cord to a com-
10
patible PDU model.
20-Amp Branch-Rated AC Output Breakers (PDUB30 Only): Control power to the PDU's outlets.
11
PDUB15
PDUB20
PDUB30
12A MAX.
UPS
AVAILABLE
UPS
OUTPUT
TO UPS OUTPUT
12A MAX.
1
6
15A MAX.
UPS
AVAILABLE
UPS
OUTPUT
TO UPS OUTPUT
15A MAX.
1
6
11
UPS
AVAILABLE
LOAD1
UPS
20A OUTPUT
OUTPUT 20A MAX.
BREAKERS
PUSH TO RESET
LOAD2
2
11
8
10
MAINTENANCE BYPASS
CONNECT UPS
AVAILABLE
LINE CORD HERE
UTILITY
UTILITY
7
9
8
10
MAINTENANCE BYPASS
CONNECT UPS
AVAILABLE
LINE CORD HERE
UTILITY
UTILITY
7
9
8
6
10
MAINTENANCE BYPASS
AVAILABLE
TO
30A
UPS OUTPUT
UTILITY
UTILITY
7
9
4
12A MAX.
OUTPUT
12A MAX.
1
16A MAX.
OUTPUT
16A MAX.
2
CONNECT UPS
LINE CORD HERE
30A
OUTPUT
24A MAX.
3