Important Safety Warnings; Mounting - Tripp-Lite PDUB15 Guide De L'utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Important Safety Warnings

SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation and operation of this product.
• Install the PDU indoors, away from excess moisture or heat, direct sunlight, dust or conductive contaminants. Do not install the PDU near
magnetic storage media, as this may cause data corruption.
• Only operate the PDU at indoor temperatures between 32° F and 104° F (0 °C and 40° C). For best results, maintain indoor temperatures
between 62° F and 84° F (17° C and 29° C). For proper ventilation, leave adequate space around all sides of the PDU.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
• Do not connect the PDU to an ungrounded outlet or to adapters that eliminate the connection to ground. The ground connections are provided
for your safety. If the provided plug does not fit your outlet, have a compatible grounded outlet installed by a qualified electrician.
• The PDU must be installed near the wall outlet and all plugs must be readily accessible for disconnection.
• The PDU must be connected to a wall outlet that is protected by an overcurrent device with the rating shown in the table below:
Model
Overcurrent Rating of Protection Device
PDUB15
20A
PDUB20
20A
30A
PDUB30
• Caution! Risk of electrical shock! The PDU is supplied by more than one power source. All power sources must be disconnected to de-
energize the unit before servicing.
• Do not open the PDU for any reason. There are no user-serviceable parts inside.

Mounting

Mounting (2-Post or 4-Post Racks)
Mount the equipment in either a 2-post or 4-post open frame rack or rack enclosure. The user must determine the fitness of hardware and
procedures before mounting. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate
for all applications. Note: Mounting procedures are the same for both 2-post and 4-post rack installation.
Step 1. Attach the mounting ears to the mounting holes of the PDU using the screws provided.
The ears should face forward. Note: The top or bottom mounting holes of the PDU can
be used.
Step 2. Attach the PDU to the rack with user-provided screws, nuts and washers. Insert the
screws through the mounting ears and into the rack rails.
Mounting in the Same Rack Space as a UPS System (4-Post Racks)
The Hot-Swap PDU can be mounted in the same rack space as a UPS system when the UPS
system is mounted using Tripp Lite's 4POSTRAILKIT. (4POSTRAILKIT is included with
most Tripp Lite UPS systems and is also sold separately. Refer to the UPS system manual or
4POSTRAILKIT manual for UPS system mounting instructions. The procedure for mounting
the rear of the 4POSTRAILKIT mounting shelves to the rack will differ slightly, as shown in this
section.)
Step 1.
Attach the mounting ears to the lower mounting holes of the unit using the screws
provided. The ears should face forward.
Model
Overcurrent Rating of Protection Device
20A (
TUV
PDUBHV10
C
20A (
TUV
PDUBHV20
C
Step 1
Step 2
Step 1
2
) or 16A (CE)
US
) or 16A (CE)
US
Mount in top or
bottom holes.