3.4 Power supply of the CPX terminal
Note
Power supply through the interlinking block with additional
power supply for electric outputs (CPX-(M)-GE-EV-Z...) does
not work with the CTEL master module, since the corres-
ponding contact rails do not have contacts.
The operating and load voltage supplies for the CPX
terminal are fed in via interlinking blocks.
The interlinking blocks carry the operating and load
voltage on to the adjacent modules.
1
1
Interlinking block with system
supply, e.g. type CPX-GE-EV-S
2
Interlinking block without supply,
e.g. type CPX-GE-EV
3
Interlinking block with additional
power supply, e.g. type
CPX-GE-EV-V
4
Load voltage for the valves
24
2
M18
3
M18
5
Load voltage for digital
outputs (not used here)
6
Operating voltage for
electronics and sensors
7
Earth terminal (functional
earth, FE)
Festo CPX-CTEL-Z6 1205NH English
4
5
6
7