Operation
The XAL127 loop expander card provides an additional device
loop on the control panel. The card expands the control panel's
device capability to 254 device addresses total, 127 per loop
(any combination of detectors and modules).
Installation
The loop expander card connects to connector J7 on the main
circuit board.
Note:
Installation limits are under the jurisdiction of local
authority.
To install the loop expander card:
1.
Power down the panel and disconnect the batteries.
2.
Locate connector J7 on the main circuit board. It is below
the primary loop card.
3.
Connect the card to connector J7 as shown in the
installation diagram. Make sure you properly align the
connector pins and plastic mounting standoffs so that they
lock into place.
4.
Connect the field wiring. See "Wiring."
5.
Power up the panel and connect the batteries.
© 2013 UTC Fire & Security. All rights reserved.
Figure 1: XAL127 installation
Wiring
The card provides either Class B or Class A wiring options.
Figure 2: Class B wiring
Loop SEC
+
Loop PRI
+
Loop card
1 / 4
Primary loop card
Connector J7
Plastic mounting
standoffs
Loop expander
card
Data line
Loop
Loop
device
device
P/N 3101093 • REV 03 • REB 28JAN13

Publicité

loading

Sommaire des Matières pour Edwards XAL127

  • Page 1 Figure 1: XAL127 installation EN: Installation Sheet Operation The XAL127 loop expander card provides an additional device loop on the control panel. The card expands the control panel's Primary loop card device capability to 254 device addresses total, 127 per loop (any combination of detectors and modules).
  • Page 2 Class A. Comm is overall loop communication. Fonctionnement Figure 5: Loop card LEDs Le carte de survoltage de boucle XAL127 procure une boucle supplémentaire au panneau de commande. La carte augmente Comm la capacité du panneau de commande à 254 adresses, soit...
  • Page 3 « Filage ». Rétablissez l’alimentation au panneau et rebranchez les piles. Figure 1 : Installation du XAL127 Voyants DEL du XAL127 Il y a trois voyants DEL sur la carte qui indiquent l'état de communication de la boucle. Il y a en premier le circuit de communication principal.
  • Page 4 Fiche technique du XAL127 Adresse du dispositif sur la Maximum de 127 (toute combinaison de boucle détecteurs et de modules) Filage Classe B ou classe A Tension de service 24 VDC Courant opérationnel En attente : 55 mA (boucle pleine charge)