CONFIGURATION

DIPSWITCHES

The dipswitch on the 50M56 control is used to determine the
length of the heat delay-to-fan-off period and cool delay-to-fan-
off period. The following table shows the time periods that will
result from the various switch positions.
COOL "OFF" DELAY
SW1-1
SECS.
ON
0*
OFF
80
*Factory Setting
OPERATION

HEAT MODE

Output
Thermostat - W
Inducer
Pressure Switch
Ignitor (HSI)
Gas Valve
Flame Sensor (FS)
Blower (Heating
Speed)
Humidifier (120V)
EAC
* Default
4
HEAT "OFF" DELAY
SW1-2
SW1-3
SECS.
ON
OFF
ON
ON
100*
OFF
ON
OFF
OFF
0 sec 17-21 sec < 5 sec 45 sec
1
2
3
60
OFF
140
180
Heating until Thermostat
is Satisfied
COOL OFF
HEAT OFF
ON
Blower Off Delay
5 sec 60/100*/140/180 sec