Fault
Reason
Does not switch
No power
(green LED does not light up)
Electronic defect
Contacts welded together
(after short-circuit)
Measuring transmitter
defective
Switches
Incorrect setting of
incorrectly
change-over switch for limit
signal in FTW 325
Permanent
Interrupt or short-circuit line to
alarm signal
measuring transmitter
Measuring transmitter
electronics defective
Nivotester defective
Endress+Hauser
Remedy
Check power
Replace FTW 325
Replace FTW 325;
connect a fuse into contactor
circuit
Replace measuring transmitter
Correctly set change-over
switch behind front panel
Check line
Replace measuring transmitter
electronics
Replace Nivotester
Trouble-shooting